GWA
Gas-Fired Water Boilers –
Boiler Manual
6
Part Number 670 01 1001 00
Air openings
continued
2
Prepare boiler
Table 3
Manifold orifice sizing
Place boiler/crate near position
1.
Leave boiler in crate and on pallet until installation site is
ready.
2. Move entire crate and pallet next to selected location.
3. Remove crate. Leave boiler on pallet.
4. Remove boiler from pallet as follows:
a. Tilt left side of boiler up and place a board under left legs.
b.
Tilt boiler the other way and place a board under right legs.
c. Slide boiler backwards off pallet and into position.
Do not drop boiler or bump jacket on floor or pallet.
Damage to boiler can result.
5. Check level.
a. Shim legs, if necessary.
b.
Do not alter legs.
Placement and setup
3. Level and straighten burners.
Burners must be properly seated in slots in burner
rest with their openings face up. Main burner orifices
must inject down center of burner. Failure to properly
seat burners will result in severe personal injury,
death or substantial property damage.
4. Reinstall access panel.
Do not operate boiler without access panel secured
in place. Failure to comply could cause momentary
flame rollout on ignition of main flame, resulting in
possible fire or personal injury hazard.
Inspect orifices and burners
1. Remove front jacket door. Remove base access panel (See
Figure 17, item 4, page 30).
2. Check for correctly-sized manifold orifices. See Table 3 for sizing.
(The orifice size is stamped on the orifice spud barrel.)
Correctly-sized manifold orifices must be used. Failure
to do so will result in severe personal injury, death or
substantial property damage.
1
Prepare boiler location
continued
Exhaust fans and air movers
The appliance space must never be under a negative pressure.
Always provide air openings sized not only to the dimensions
required for the firing rate of all appliances, but also to handle the air
movement rate of the exhaust fans or air movers using air from the
building or space.
Motorized air dampers
If the air openings are fitted with motorized dampers, electrically
interlock the damper to:
•
Prevent the boiler from firing if the damper is not fully open.
•
Shut the boiler down should the damper close during boiler
operation.
To accomplish this interlock, wire an isolated contact (proving the
damper open) in series with the thermostat input to the boiler. The
boiler will not start if this contact is open, and will shut down should
it open during operation.
Location
Natural gas
Propane gas
U. S.
Sea level –
2,000 ft
over
2,000 ft
Sea level –
2,000 ft
over
2,000 ft
2.00 mm
(Note 1)
1.30 mm
(Note 1)
Canada
Sea level –
2,000 ft
2,000 –
4,500
Sea level –
2,000 ft
2,000 –
4,500
2.00 mm
# 49
1.30 mm
# 56
Note 1:
For U. S. elevations above 2,000 feet, contact your International Com-
fort Products supplier for details.
GWA
Gas-Fired Water Boilers –
Boiler Manual
31
Part Number 670 01 1001 00
Figure 18
Jacket assembly
12 Replacement parts
continued
The boiler contains ceramic fiber and fiberglass materials. Use care when handling these materials per
instructions on page 23 of this manual. Failure to comply could result in severe personal injury.
Item
number
Description
International
Comfort
Products
part number
1
Junction box, 4 x 4
(Available at local supply house)
1a
Junction box, 2 x 4
(Available at local supply house)
2
Jacket panel, left side, with
insulation
431223425WT
3
Jacket panel, right side, with
insulation
431223426WT
4
Jacket
panel,
door
GWA052 & GWA070
GWA105
GWA140
GWA175
GWA210
GWA245
431223450WT
431223451WT
431223452WT
431223453WT
431223454WT
431223455WT
Item
number
Description
International
Comfor t
Products
par t number
5
Jacket
panel, top
GWA052 & GWA070
GWA105
GWA140
GWA175
GWA210
GWA245
431223433WT
431223434WT
431223435WT
431223436WT
431223437WT
431223438WT
6
Jacket
cross tie
GWA052 & GWA070
GWA105
GWA140
GWA175
GWA210
GWA245
431223507WT
431223508WT
431223509WT
431223510WT
431223511WT
431223512WT
7
Jacket
panel,
interior,
with
insulation
GWA052 & GWA070
GWA105
GWA140
GWA175
GWA210
GWA245
431223427WT
431223428WT
431223429WT
431223430WT
431223431WT
431223432WT
8
Jacket
panel,
rear, with
insulation
GWA052 & GWA070
GWA105
GWA140
GWA175
GWA210
GWA245
431223444WT
431223445WT
431223446WT
431223447WT
431223448WT
431223449WT