background image

GWA

 

Gas-Fired Water Boilers – 

Boiler Manual

7

Part Number 670 01 1001 00

Perform hydrostatic pressure test

Pressure test boiler before attaching water or gas piping  or electrical
supply (except as noted below).

Prepare boiler for test

1. Remove the shipping nipple (from GWA supply tapping) and

remove the boiler relief valve. Temporarily plug the relief valve
tapping with a ¾" NPT pipe plug.

2. Remove 1¼" nipple, reducing tee and drain valve from

accessory bag. Install in boiler return connection as shown on
in Figure 19, item 3, page 32. Install circulator on either the
return or supply.

3. Remove 1¼" nipple, 1¼" tee, bushing and pressure/temperature

gauge from accessory bag. Pipe to boiler supply connection as
shown in Figure 19, item 2, page 32. (Use pipe dope sparingly.)

4. Connect a hose to boiler drain valve, the other end connected

to a fresh water supply. Make sure hose can also be used to
drain boiler after test.

5. Connect a nipple and shutoff valve to system supply connection

on the 1¼" tee. This valve will be used to bleed air during the fill.
(Valve and nipple are not included with boiler.)

6. Connect a nipple and shutoff valve to system return connection

(at circulator flange if circulator installed on return). This valve
will be used to bleed air during the fill. (Valve and nipple are not
included with boiler.)

7. Temporarily plug the air elimination tapping (next to supply

tapping).

2

Prepare boiler 

continued

Pressure test

Fill and pressure test

1. Open the shutoff valves you installed on supply and return

connections.

2. Slowly open boiler drain valve and fresh water supply to fill

boiler with water.

3. When water flows from shutoff valves, close boiler drain valve.

4. Close shutoff valves.

5. Slowly reopen boiler drain valve until test pressure of not more

than 45 psi is reached on the pressure/temperature gauge.

6. Test at no more than 45 psi for no more than 10 minutes.

Do not leave boiler unattended. A cold water fill could
expand and cause excessive pressure, resulting in
severe personal injury, death or substantial property
damage.

7. Make sure constant gauge pressure has been maintained

throughout test. Check for leaks. Repair if found.

Leaks must be repaired at once. Failure to do so can
damage boiler, resulting in substantial property
damage.

Do not use petroleum-based cleaning or sealing
compounds in boiler system. Severe damage to boiler
will occur, resulting in substantial property damage.

Drain and remove fittings

1. Disconnect fill water hose from water source.

2. Drain boiler at drain valve or out hose, whichever provides best

access to drain. Remove hose after draining if used to drain
boiler.

3. Remove nipples, valves and plus unless they will remain for

use in the system piping.

4. Remove plug from relief valve tapping. See Section 3, page 10,

to replace relief valve.

GWA

 

Gas-Fired Water Boilers – 

Boiler Manual

30

Part Number 670 01 1001 00

Figure 17

Base assembly, manifold, orifices and burners

12 Replacement parts 

continued

It em

number

D esc ript ion

Int ernat ional

C omf ort

P roduc t s

part number

Base assembly kit

GWA052 & GWA070
GWA105
GWA140
GWA175
GWA210
GWA245

381354200WT

381354201WT
381354202WT
381354203WT
381354204WT
381354205WT

1

Base side panel (in Base assembly)

2

Base front cross-tie assembly (in Base assembly)

3

Base back cross-tie assembly (in Base assembly)

4

Base access panel (in Base assembly)

5

Base pan angle, left side (in Base assembly)

6

Base pan angle, right side (in Base assembly)

7

Base pan (in Base assembly)

8

Burner rest (in Base assembly)

9

Base insulation kit
(includes insulation for
all base parts above
plus gasket material
needed between block
assembly and base)

GWA052 to GWA140
GWA175 to GWA245

381354210WT

381354211WT

10

Boiler leg kit

590424252WT

11

Manifold

GWA052
GWA070
GWA105
GWA140
GWA175
GWA210
GWA245

591126615WT
591126616WT
591126617WT
591126618WT
591126619WT
591126556WT
591126557WT

12

Main burner orifice, sea level

560528997WT

13

Burner, stainless steel

512200077WT

14

Burner with pilot
bracket
(not shown)

Standing pilot

512200079WT

Spark-ignited pilot

512200078WT

15

Screw, 10-32 x

3

/

8

STP type D hx, washer head

slot ZP

available at

local supply

house

16

Rollout thermal fuse element

512050230WT

Summary of Contents for GWA 245

Page 1: ...Hazards that will or can cause minor personal injury or property damage Special instructions on installation operation or maintenance that are important but not related to personal injury or property...

Page 2: ......

Page 3: ...ation dimensions Residential garage installation Take the following special precautions when installing the boiler in a residential garage If the boiler is located in a residential garage per ANSI Z22...

Page 4: ......

Page 5: ...n 12 inches of the ceiling the other within 12 inches of the floor as shown in the table illustrations Provide adequate combustion and ventilation air to assure proper combustion and reduce the risk o...

Page 6: ......

Page 7: ...ded with boiler 7 Temporarily plug the air elimination tapping next to supply tapping 2 Prepare boiler continued Pressure test Fill and pressure test 1 Open the shutoff valves you installed on supply...

Page 8: ......

Page 9: ...the damper blade 3 Install damper harness between damper actuator and hole in jacket left side panel See Figure 3 page 8 Use strain relief connectors and locknuts to secure both ends of damper harnes...

Page 10: ......

Page 11: ...ation Failure to prevent low return water temperature to the boiler could cause corrosion of the boiler sections or burners resulting in severe personal injury death or substantial property damage Ins...

Page 12: ......

Page 13: ...8 79 150 305 460 150 31 64 120 250 380 1 Remove jacket front panel and see Figure 10 to pipe gas to boiler a Install drip leg at inlet of gas connection to boiler Where local utility requires drip leg...

Page 14: ......

Page 15: ...ragm type or bladder type expansion tank systems only one turn 5 Open other vents a Starting on the lowest floor open air vents one at a time until water squirts out b Repeat with remaining vents 6 Re...

Page 16: ......

Page 17: ...to verify operation 5 Return thermostat to normal setting 6 Set thermostat heat anticipator setting indicated on wiring diagram Check venting system operation 1 With boiler firing hold a candle or mat...

Page 18: ......

Page 19: ...d on boiler Vent damper will remain closed until a call for heat 2 Call for heat When thermostat circuit closes the boiler circulator and vent damper are energized The vent damper drives open When the...

Page 20: ......

Page 21: ...inspect the appliance and to replace any part of the control system and any gas control which has been under water 1 Stop Read the safety information above on this label 2 Set the thermostat to lowes...

Page 22: ......

Page 23: ...lace it in a plastic bag for disposal Wash potentially contaminated clothes separately from other clothing Rinse clothes washer thoroughly NIOSH stated First Aid Eye Irrigate immediately Breathing Fre...

Page 24: ......

Page 25: ...tomatic air vents in systems with closed type tanks The air will escape from the system instead of returning to the tank Eventually the tank will waterlog and no longer control pressurization The boil...

Page 26: ......

Page 27: ...ow Lighting Instructions pages 20 and 21 If gas is available and you cannot obtain a pilot flame try purging the gas line and cleaning pilot and pilot gas tubing Follow Lighting Instructions again If...

Page 28: ......

Page 29: ...2 GWA070 GWA105 GWA140 GWA175 GWA210 GWA245 450021270WT 450021271WT 450021272WT 450021273WT 450021274WT 450021275WT 450021276WT Item number Description International Comfort Products part number 4 Hig...

Page 30: ......

Page 31: ...T 4 Jacket panel door GWA052 GWA070 GWA105 GWA140 GWA175 GWA210 GWA245 431223450WT 431223451WT 431223452WT 431223453WT 431223454WT 431223455WT Item number Description International Comfort Products pa...

Page 32: ......

Page 33: ...rt number Standing pilot Natural gas components 1 Gas valve 1 2 x 1 2 GWA052 through GWA175 Gas valve 3 4 x 3 4 GWA210 and GWA245 Honeywell Robertshaw Honeywell VR8200A2116 7200ER VR8300C4050 51104436...

Page 34: ......

Page 35: ...after the model number designates natural gas The letter after the N designates the pilot ignition system S for standing pilot or I for spark ignited pilot For example a suffix NS means a natural sta...

Page 36: ......

Reviews: