background image

441 01 2314 06

Specifications are subject  to change without notice.

26

NOTE: It is very important to reinstall the NOx insert mounting

screws.

Figure 22

Removing NOx inserts

Representative drawing only, some models may vary in appearance.

Main Burner Flame Check

Allow the furnace to run approximately 10 minutes. Then inspect

the main burner and pilot flames. See 

Figure 23

.

Check for the following (

Figure 23

):

Stable and blue flames. Dust may cause orange tips or wisps

of yellow, but flames 

MUST NOT

 have solid, yellow tips.

Flames extending directly from burner into heat exchanger.

Flames do 

NOT

 touch sides of heat exchanger

If any problems with main burner flames are noted, it may be nec-

essary to adjust manifold gas pressure, or check for drafts.

Main Burner

Burner Face

10

10

78

Figure 23

NOTE: For Ignitor location see 

Figure 24.

Ignitor Location 

in (mm)

Figure 24

5

/

16

(8)

1

/

4

(6.4)

2

1/

16

(52.4)

25-25-08

NOTE:

 Flame sensor has a different orientation in all 050 models.

Air Temperature Rise Check

!

REDUCED FURNACE LIFE HAZARD
Failure to follow this caution may result in reduced

furnace life.

Use 

ONLY 

the blower motor speed taps insert

indicated in the 

Circulation Air Blower Data

 for

setting air temperature rise.

CAUTION

The blower speed 

MUST

 be set to give the correct air temperature

rise through the furnace as marked on the rating plate. Tempera-

ture rise is the difference between supply and return air tempera-

tures.

To check temperature rise, use the following procedure:
1. Place thermometers in supply and return air registers as close

to furnace as possible, avoiding direct radiant heat from heat

exchangers.

2. Operate furnace for 10 minutes with all the registers and duct

dampers open by using a jumper wire on R to W thermostat

connections on the control board.

3. Take readings and compare with range specified on rating

plate.

4. If the air temperature rise is not in the correct range, the blow-

er speed must be changed. A higher blower speed will lower

the temperature rise. A lower blower speed will increase the

temperature rise.

5. Remove the jumper wire after the adjustments are complete.

Changing Blower Speed

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in

personal injury or death.
Turn OFF power to furnace, lockout and tag with a

suitable warning label, before changing speed

taps.

!

WARNING

NOTE

: The speed taps that the manufacturer sets at  the factory

for this furnace are based on a nominal 400 CFM per ton cooling

and the basic mid range on the temperature rise for heating.

Since the manufacturer cannot predict the static pressure

that will be applied to the furnace, it is the responsibility of the

installer dealer/contractor to select the proper speed tap

leads for the application when the furnace is installed.

If it is necessary to change speeds, refer to steps below.
1. Refer to 

Furnace Wiring Diagram

 for location of the heating

and cooling speed taps located on the furnace control as well

as location of unused blower motor speed leads. Use the

chart (

Table 7

) to determine the blower motor speed settings.

Table 7

 Blower Speed Chart

Wire Color

Motor Speed

Black

High

Orange

*

Med

High

Blue

Med

Low

Red

Low

*

 Med

High speed may not be provided on all models.

Summary of Contents for C8DNL

Page 1: ...injury TABLE OF CONTENTS SAFETY CONSIDERATIONS 2 Safe Installation Requirements 3 INSTALLATION 4 Combustion Ventilation Air 6 Gas Vent Installation 9 Venting Horizonta 10 Venting Chimney Adapter 12 Ga...

Page 2: ...nformation This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand these signal words DANGER WARNIN...

Page 3: ...e ON setting ____ Fan Time OFF Setting ___ Manual Gas Shut Off Upstream of Furnace Drip Leg Gas Valve turned ON Type of Gas Natural Propane Filter Type and Size Calculated Firing Rate See Checks and A...

Page 4: ...around supply and return air ducts Install correct filter type and size Unit MUST be installed so electrical components are pro tected from direct contact with water Safety Rules Your unit is built to...

Page 5: ...ible material See Ductwork and Filter Sub base for Com bustible Floors 6 Maintain clearance for fire safety and servicing A front clear ance of 24 609 6mm required and 30 762mm recommen ded for access...

Page 6: ...ion Line contact is permissible only between lines formed by intersections of top and two sides of furnace jacket and building joists studs or framing DIMENSIONAL INFORMATION Unit Capacity Cabinet Top...

Page 7: ...gens that will result in safety and performance related problems and may harm the furnace These instances must use only out door air for combustion The following areas or types of structures may cont...

Page 8: ...Not less than the sum of the areas of all vent connectors in the space The opening shall commence within 12 304 8mm of the top of the enclosure Appliances shall have clearances of at least 1 25 4mm f...

Page 9: ...0 20 3 150 88 2 4 200 117 6 5 250 147 3 750 105 5 625 157 5 7 500 210 9 375 262 5 11 250 316 0 10 6 300 176 4 8 400 235 2 10 500 294 7 500 210 11 250 315 15 000 420 18 750 525 22 500 632 0 00 NP NP NP...

Page 10: ...pipe as per mitted by the National Fuel Gas Code Code ANSI Z223 1 NFPA 54 2009 Sections 12 and 13 venting requirements in the United States or the National Standard of Canada Natural Gas and Pro pane...

Page 11: ...st be lined with either Type B vent sized in accordance with NFGC tables 13 1 or 13 2 or a listed metal lining system sized in accordance with the NFGC Section 13 1 7 for a single appliance or 13 2 20...

Page 12: ...dryer or water heater vent or other appliance s direct vent intake or exhaust N Clearance to the vent terminal of a dryer vent water heater vent or other appliances direct vent intake or exhaust O Cle...

Page 13: ...s are for use with ONLY furnaces having a Chimney Adapter Kit number marked on the furnace rating plate WARNING If a clay tile lined masonry chimney is being used and it is exposed to the outdoors bel...

Page 14: ...vent in a chase If a metal liner or Type B vent is used to line a chimney no other appliance shall be vented into the annular space between the chimney and the metal liner APPLIANCE APPLICATION REQUI...

Page 15: ...anufacturer s installation instructions CHIMNEY INSPECTION CHART For additional requirements refer to the National Fuel Gas Code ANSI Z223 1 NFPA 54 2009 and ANSI NFPA 211 2006 Chimneys Fire places Ve...

Page 16: ...ose to the furnace as possible where it is readily ac cessible Refer to Figure 7 FIRE HAZARD Failure to follow this warning could result in personal injury death and or property damage Use wrench to h...

Page 17: ...rnace Black iron pipe shall be installed at the furnace gas control valve and extend a minimum of 2 50 8mm outside furnace WARNING Additional Propane Piping Requirements Have a licensed Propane gas de...

Page 18: ...Box to alternate location and attach using two self tapping screws from bag 5 A wire tie may need to be cut for additional wire length 6 Apply two hole plugs from bag at left J Box location 7 Positio...

Page 19: ...trical shorts of 24V wiring during installation service or maintenance may cause fuse to blow If fuse replacement is required use only a fuse of identical size 5 amp FUSE 25 24 98 Diagnostic Light Jum...

Page 20: ...er is in the full heat or cool position Installation of locking type dampers is recommended in all branches or in individual ducts to balance system s air flows Non combustible flexible duct connector...

Page 21: ...15 381 221 2 571 5 Subbase for Coil Box NAHH004SB 153 4 25 4 209 16 522 3 149 16 369 9 161 16 408 161 4 412 8 145 8 371 5 15 381 131 2 342 9 15 381 131 2 342 9 NAHH005SB 193 8 181 1 209 16 522 3 183...

Page 22: ...e return air plenum above the furnace A filter rack is supplied with each furnace See Figure 17 Use either filter type Washable high velocity filters are based on a maximum air flow rating of 600 FPM...

Page 23: ...d pull straight down at side of blower Pull out through right door opening 4 Vacuum clean or wash with warm water and dry thoroughly be fore replacing NOTE If filters are only suitable for heating app...

Page 24: ...rol Remove manometer connection from manifold pressure tap and replace plug in gas valve 7 Check for leaks at plug Typical Gas Control Valve Figure 19 Regulator Adjustment Under Cap Inlet Pressure Tap...

Page 25: ...in accordance with the Manufacturer s instructions and all applicable codes and requirements or in the absence of local codes the applicable national codes WARNING MANIFOLD PRESSURE AND ORIFICE SIZE F...

Page 26: ...e burner compartment 2 Disconnect gas line from gas control valve so manifold can be removed 3 Disconnect wiring at gas control valve Be sure to note the proper location of all electrical wiring befor...

Page 27: ...ply and return air registers as close to furnace as possible avoiding direct radiant heat from heat exchangers 2 Operate furnace for 10 minutes with all the registers and duct dampers open by using a...

Page 28: ...he continuous fan option This connection is intended for the low speed motor tap and has a lower contact rating 8 amps than the heat and cool taps When the low speed blower lead is connected to this t...

Page 29: ...continuously while there are no other blower demands from furnace control Fan demands from furnace control for heat cool or G will override hard wired speed tap NOTE 3 EAC is NOT active for hard wired...

Page 30: ...c Codes See Figure 25 OFF 24VAC or 115VAC is off fuse is open Heartbeat Normal operation or no previous Diagnostic Code ON SOLID Soft Lockout Furnace Control Error 1 hr delay If code repeats immediate...

Page 31: ...ubject to change without notice Save This Manual For Future Reference Downflow Models 8DNL050B12B2 8DNL075B12B2 8DNL075F16B2 8DNL100F14B2 8DNL100L20B2 8DNL125L20B2 Denotes Brand International Comfort...

Page 32: ...han 4 480oF 264oC 4 480oF 264oC 4 480oF 264oC 4 480oF 264oC 4 480oF 264oC 4 480oF 264oC Limits Controls Thermal Sensor oF oC Limit Control 300 149 See Parts List 300 149 See Parts List 300 149 See Par...

Page 33: ...Liters per second Filter required for each return air inlet Airflow performance includes 1 25 4mm washable 600 FPM 3 0 m s max filter media See Table for bellyband location on motor 8DNL100F14 1 Exter...

Page 34: ...441 01 2314 06 Specifications are subject to change without notice 33 Wiring Diagram 8DNL...

Page 35: ...njury or property damage Consult a qualified installer service agency local gas supplier or your distributor or branch for information or assistance The qualified installer or agency must use only fac...

Reviews: