background image

441 01 2314 06

Specifications are subject  to change without notice.

13

Exterior Masonry Chimney,

FAN+NAT Installations with

Type

B Double

Wall Vent Connectors

                                       

 

NFPA & AGA

Table A-

Combined Appliance

Maximum Input Rating in

Thousands of Btu per Hr

VENT

HEIGHT

FT(m)

INTERNAL AREA OF CHIMNEY

SQ IN.(mm)

12(77.4)

19(122.6)

28(180.6)

38(245.2)

6(1.8)

74

119

178

257

8(2.4)

80

130

193

279

10(3)

84

138

207

299

15(4.6)

NR

152

233

334

20(6.1)

NR

NR

250

368

30(9.1)

NR

NR

NR

404

Table B-

Minimum Allowable Input Rating of

Space-Heating Appliance in

Thousands of Btu per Hr

VENT

HEIGHT

FT(m)

INTERNAL AREA OF CHIMNEY

sq. in(mm)

12(77.4)

19(122.6)

28(180.6)

38(245.2)

17 to 26

F (

8 to 

3

C)

Local 99% Winter Design Temperature:

17 to 26

°

F (

8 to 

3

°

C)*

6(1.8)

0

55

99

141

8(2.4)

52

74

111

154

10(3)

NR

90

125

169

15(4.6)

NR

NR

167

212

20(6.11)

NR

NR

212

258

30(9.1)

NR

NR

NR

362

5 t o 16

F (

15 to 

9

C)

Local 99%  Winter Design Temperature:

5 to 16

°

F (

15 to 

9

°

C)*

6(1.8)

NR

78

121

166

8(2.4)

NR

94

135

182

10(3)

NR

111

149

198

15(4.6)

NR

NR

193

247

20(6.11)

NR

NR

NR

293

30(9.1)

NR

NR

NR

377

10 to 4

F (

23 to 

16

C)

Local 99%  Winter Design Temperature:

10 to 4

°

F (

23 to 

16

°

C)*

6(1.8)

NR

NR

145

196

8(2.4)

NR

NR

159

213

10(3)

NR

NR

175

231

15(4.6)

NR

NR

NR

283

20(6.11)

NR

NR

NR

333

30(9.1)

NR

NR

NR

NR

11

°

F

(

24

°

C)

or lower

Local 99%  Winter Design Temperature:

 

11

°

F (

24

°

C) or lower*

Not recommended for any vent configuration

*  The 99% Winter Design Dry

Bulb (db) temperatures are

found in the 2005 ASHRAE Fundamentals Handbook CD

and Chapter 28.

Inspections before the sale and at the time of installation will deter-

mine the acceptability of the chimney or the need for repair and/or

(re)lining.  Refer to the Chimney Inspection Chart to perform a

chimney inspection.
If the inspection of a previously used tile

lined chimney:

a. Shows 

signs of vent gas condensation, the chimney should

be relined in accordance with local codes and the authority

having jurisdiction.  The chimney should be relined with a

listed metal liner or Type

B vent to reduce condensation.  If

a condensate drain is required by local code, refer to the

NFGC, Section 12.10 for additional information on conden-

sate drains.

b.  Indicates the chimney exceeds the maximum permissible

size in the tables, the chimney should be rebuilt or relined to

conform to the requirements of the equipment being

installed and the authority having jurisdiction.

A chimney without a clay tile liner, which is otherwise in good con-

dition, shall be rebuilt to conform to ANSI/NFPA 211 or be lined with

a UL listed (ULC listed in Canada) metal liner or UL listed Type

B

vent.  Relining with a listed metal liner or Type

B vent is consid-

ered to be a vent

in

a

chase.

If a metal liner or Type

B vent is used to line a chimney, no other

appliance shall be vented into the annular space between the

chimney and the metal liner.

APPLIANCE APPLICATION REQUIREMENTS

Appliance operation has a significant impact on the performance

of the venting system.  If the appliances are sized, installed, ad-

justed, and operated properly, the venting system and/or the ap-

pliances should not suffer from condensation and corrosion.  The

venting system and all appliances shall be installed in accordance

with applicable listings, standards, and codes.
The furnace should be sized to provide 100 percent of the design

heating load requirement plus any margin that occurs because of

furnace model size capacity increments.  Heating load estimates

can be made using approved methods available from Air Condi-

tioning Contractors of America (Manual J); American Society of

Heating, Refrigerating, and Air

Conditioning Engineers; or other

approved engineering methods.  Excessive oversizing of the fur-

nace could cause the furnace and/or vent to fail prematurely.
When a metal vent or metal liner is used, the vent or liner must be in

good condition and be installed in accordance with the vent or liner

manufacturer’s instructions.
To prevent condensation in the furnace and vent system, the fol-

lowing precautions must be observed:

1. The 

return

air temperature must be at least 60

°

F(16

°

C) db

except for brief periods of time during warm

up from set-

back at no lower than 55

°

F(13

°

C) db or during initial start

up from a standby condition.

2.  Adjust the gas input rate per the installation instructions.

Low gas input rate causes low vent gas temperatures, caus-

ing condensation and corrosion in the furnace and/or vent-

ing system.  Derating is permitted only for altitudes above

2000

 (610m).

3.   Adjust the air temperature rise to the midpoint of the rise

range or slightly above.  Low air temperature rise can cause

low vent gas temperature and potential for condensation

problems.

4.  Set the thermostat heat anticipator or cycle rate to reduce

short cycling.

Air for combustion must not be contaminated by halogen com-

pounds which include chlorides, fluorides, bromides, and iodides.

These compounds are found in many common home products

such as detergent, paint, glue, aerosol spray, bleach, cleaning sol-

vent, salt, and air freshener, and can cause corrosion of furnaces

and vents.  Avoid using such products in the combustion

air sup-

ply.  Furnace use during construction of the building could cause

the furnace to be exposed to halogen compounds, causing prema-

ture failure of the furnace or venting system due to corrosion.
Vent dampers on any appliance connected to the common vent

can cause condensation and corrosion in the venting system.  Do

not use vent dampers on appliances common vented with this fur-

nace.

Summary of Contents for C8DNL

Page 1: ...injury TABLE OF CONTENTS SAFETY CONSIDERATIONS 2 Safe Installation Requirements 3 INSTALLATION 4 Combustion Ventilation Air 6 Gas Vent Installation 9 Venting Horizonta 10 Venting Chimney Adapter 12 Ga...

Page 2: ...nformation This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand these signal words DANGER WARNIN...

Page 3: ...e ON setting ____ Fan Time OFF Setting ___ Manual Gas Shut Off Upstream of Furnace Drip Leg Gas Valve turned ON Type of Gas Natural Propane Filter Type and Size Calculated Firing Rate See Checks and A...

Page 4: ...around supply and return air ducts Install correct filter type and size Unit MUST be installed so electrical components are pro tected from direct contact with water Safety Rules Your unit is built to...

Page 5: ...ible material See Ductwork and Filter Sub base for Com bustible Floors 6 Maintain clearance for fire safety and servicing A front clear ance of 24 609 6mm required and 30 762mm recommen ded for access...

Page 6: ...ion Line contact is permissible only between lines formed by intersections of top and two sides of furnace jacket and building joists studs or framing DIMENSIONAL INFORMATION Unit Capacity Cabinet Top...

Page 7: ...gens that will result in safety and performance related problems and may harm the furnace These instances must use only out door air for combustion The following areas or types of structures may cont...

Page 8: ...Not less than the sum of the areas of all vent connectors in the space The opening shall commence within 12 304 8mm of the top of the enclosure Appliances shall have clearances of at least 1 25 4mm f...

Page 9: ...0 20 3 150 88 2 4 200 117 6 5 250 147 3 750 105 5 625 157 5 7 500 210 9 375 262 5 11 250 316 0 10 6 300 176 4 8 400 235 2 10 500 294 7 500 210 11 250 315 15 000 420 18 750 525 22 500 632 0 00 NP NP NP...

Page 10: ...pipe as per mitted by the National Fuel Gas Code Code ANSI Z223 1 NFPA 54 2009 Sections 12 and 13 venting requirements in the United States or the National Standard of Canada Natural Gas and Pro pane...

Page 11: ...st be lined with either Type B vent sized in accordance with NFGC tables 13 1 or 13 2 or a listed metal lining system sized in accordance with the NFGC Section 13 1 7 for a single appliance or 13 2 20...

Page 12: ...dryer or water heater vent or other appliance s direct vent intake or exhaust N Clearance to the vent terminal of a dryer vent water heater vent or other appliances direct vent intake or exhaust O Cle...

Page 13: ...s are for use with ONLY furnaces having a Chimney Adapter Kit number marked on the furnace rating plate WARNING If a clay tile lined masonry chimney is being used and it is exposed to the outdoors bel...

Page 14: ...vent in a chase If a metal liner or Type B vent is used to line a chimney no other appliance shall be vented into the annular space between the chimney and the metal liner APPLIANCE APPLICATION REQUI...

Page 15: ...anufacturer s installation instructions CHIMNEY INSPECTION CHART For additional requirements refer to the National Fuel Gas Code ANSI Z223 1 NFPA 54 2009 and ANSI NFPA 211 2006 Chimneys Fire places Ve...

Page 16: ...ose to the furnace as possible where it is readily ac cessible Refer to Figure 7 FIRE HAZARD Failure to follow this warning could result in personal injury death and or property damage Use wrench to h...

Page 17: ...rnace Black iron pipe shall be installed at the furnace gas control valve and extend a minimum of 2 50 8mm outside furnace WARNING Additional Propane Piping Requirements Have a licensed Propane gas de...

Page 18: ...Box to alternate location and attach using two self tapping screws from bag 5 A wire tie may need to be cut for additional wire length 6 Apply two hole plugs from bag at left J Box location 7 Positio...

Page 19: ...trical shorts of 24V wiring during installation service or maintenance may cause fuse to blow If fuse replacement is required use only a fuse of identical size 5 amp FUSE 25 24 98 Diagnostic Light Jum...

Page 20: ...er is in the full heat or cool position Installation of locking type dampers is recommended in all branches or in individual ducts to balance system s air flows Non combustible flexible duct connector...

Page 21: ...15 381 221 2 571 5 Subbase for Coil Box NAHH004SB 153 4 25 4 209 16 522 3 149 16 369 9 161 16 408 161 4 412 8 145 8 371 5 15 381 131 2 342 9 15 381 131 2 342 9 NAHH005SB 193 8 181 1 209 16 522 3 183...

Page 22: ...e return air plenum above the furnace A filter rack is supplied with each furnace See Figure 17 Use either filter type Washable high velocity filters are based on a maximum air flow rating of 600 FPM...

Page 23: ...d pull straight down at side of blower Pull out through right door opening 4 Vacuum clean or wash with warm water and dry thoroughly be fore replacing NOTE If filters are only suitable for heating app...

Page 24: ...rol Remove manometer connection from manifold pressure tap and replace plug in gas valve 7 Check for leaks at plug Typical Gas Control Valve Figure 19 Regulator Adjustment Under Cap Inlet Pressure Tap...

Page 25: ...in accordance with the Manufacturer s instructions and all applicable codes and requirements or in the absence of local codes the applicable national codes WARNING MANIFOLD PRESSURE AND ORIFICE SIZE F...

Page 26: ...e burner compartment 2 Disconnect gas line from gas control valve so manifold can be removed 3 Disconnect wiring at gas control valve Be sure to note the proper location of all electrical wiring befor...

Page 27: ...ply and return air registers as close to furnace as possible avoiding direct radiant heat from heat exchangers 2 Operate furnace for 10 minutes with all the registers and duct dampers open by using a...

Page 28: ...he continuous fan option This connection is intended for the low speed motor tap and has a lower contact rating 8 amps than the heat and cool taps When the low speed blower lead is connected to this t...

Page 29: ...continuously while there are no other blower demands from furnace control Fan demands from furnace control for heat cool or G will override hard wired speed tap NOTE 3 EAC is NOT active for hard wired...

Page 30: ...c Codes See Figure 25 OFF 24VAC or 115VAC is off fuse is open Heartbeat Normal operation or no previous Diagnostic Code ON SOLID Soft Lockout Furnace Control Error 1 hr delay If code repeats immediate...

Page 31: ...ubject to change without notice Save This Manual For Future Reference Downflow Models 8DNL050B12B2 8DNL075B12B2 8DNL075F16B2 8DNL100F14B2 8DNL100L20B2 8DNL125L20B2 Denotes Brand International Comfort...

Page 32: ...han 4 480oF 264oC 4 480oF 264oC 4 480oF 264oC 4 480oF 264oC 4 480oF 264oC 4 480oF 264oC Limits Controls Thermal Sensor oF oC Limit Control 300 149 See Parts List 300 149 See Parts List 300 149 See Par...

Page 33: ...Liters per second Filter required for each return air inlet Airflow performance includes 1 25 4mm washable 600 FPM 3 0 m s max filter media See Table for bellyband location on motor 8DNL100F14 1 Exter...

Page 34: ...441 01 2314 06 Specifications are subject to change without notice 33 Wiring Diagram 8DNL...

Page 35: ...njury or property damage Consult a qualified installer service agency local gas supplier or your distributor or branch for information or assistance The qualified installer or agency must use only fac...

Reviews: