2.26 ~AATnn
Description:
Sets the soft INIT timeout value.
Syntax:
~AATnn[CHKSUM](CR)
~
Delimiter character
AA
Address of the module to be set (00 to FF)
T
Command to set the soft INIT timeout
nn
Two hexadecimal digits representing the timeout
value in seconds. The maximum timeout value
is 60 seconds. When changing the Baud Rate or
checksum settings without altering the INIT*
status, the ~AAI and %AANNTTCCFF
commands should be sent consecutively and the
time interval between the two commands should
be less than the soft INIT timeout. If the soft
INIT timeout is 0, then the Baud Rate and
checksum settings cannot be changed using
software only. The power-on reset value of the
soft INIT timeout is 0.
tM-TH8