tM-TH8 User Manual, Rev: A1.1 7MH-018-A11
43
Examples:
Command: $011
Receive: !01
Performs a zero calibration on module 01 and returns
a valid response.
Command: $021
Receive: !02
Performs a zero calibration on module 02 and returns
a valid response.
Command: $031
Receive: ?03
Performs a zero calibration on module 03. An invalid
command is returned because the “enable calibration”
command was not sent in advance.
Related Commands:
Section 2.4 $AA0, Section 2.21 ~AAEV
Related Topics:
Section 1.9 Calibration
Notes:
The “enable calibration” command, ~AAEV, must be sent
before this command is used, see Section 1.9 for details.
tM-TH8