2.10 $AA7CiRrr
Description:
Sets the type code of a channel.
Syntax:
$AA7CiRrr[CHKSUM](CR)
$
Delimiter character
AA
Address of the module to be set (00 to FF)
7
Command to set the channel range code
Ci
i specifies the input channel to be set (0-7)
Rrr
rr represents the type code of the channel to be
set. Refer to the Temperature Sensor Type
Setting table in Section 1.10.
Response:
Valid command:
!AA [CHKSUM](CR)
Invalid command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command or
invalid type code
AA
Address of the responding module (00 to FF)
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.
tM-TH8