PM
-
3133i User
’s Manual v1.02
Last Revised: Apr. 2023 Page: 27
Copyright © ICP DAS Co., Ltd. All Rights Reserved.
E-mail: [email protected]
PF_tot
34417-34418
0x1140-0x1141
DWord
Float
kWh_tot
34419-34420
0x1142-0x1143
DWord
Float
kvarh_tot
34421-34422
0x1144-0x1145
DWord
Float
kVAh_tot
34423-34424
0x1146-0x1147
DWord
Float
Freq_a
34425-34426
0x1148-0x1149
DWord
Float
45~65
Hz
Freq_b
34427-34428
0x114A-0x114B
DWord
Float
45~65
Hz
Freq_c
34429-34430
0x114C-0x114D
DWord
Float
45~65
Hz
Freq_max
34431-34432
0x114E-0x114F
DWord
Float
45~65
Hz
VTHD
34459-34460
0x116A-0x116B
DWord
Float
Phase set by
Harmonic Phase
Select
Register
ITHD
34461-34462
0x116C-0x116D
DWord
Float
Bi_Positive
_kWh
35487-35488
0x156E-0x156F
DWord
Float
Bi_Negative
_kWh
35489-35490
0x1570-0x1571
DWord
Float
Bi_Net
_kWh
35491-35492
0x1572-0x1573
DWord
Float
Bi_Total
_kWh
35493-35494
0x1574-0x1575
DWord
Float
Note:
The definition of bi-direction energy registers :
Bi_Positive_kWh: = Sum( absolute( all channel's positive kWh in every sec.))
Bi_Negative_kWh: = Sum( absolute( all channel's negative kWh in every sec.))
Bi_Net_kWh: = Sum( all channel's kWh in every sec. )
Bi_Total_kWh: = Sum( absolute( all channels kWh in every sec. ))