59
I-7011, I-7018 User Manual
Rev:B1.0
2.37 ~AA4
Description
: Read PowerOn Value and Safe Value
Syntax
:
~AA4[CHK](cr)
~
delimiter character
AA
address of reading module (00 to FF)
4
command for reading PowerOn Value and Safe Value
Response
:
Valid Command :
!AAPPSS[CHK](cr)
Invalid Command :
?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
!
delimiter for valid command
?
delimiter for invalid command
AA
address of response module(00 to FF)
PP
PowerOn Value, 00=DO0 off, DO1 off, 01=DO0 on, DO1
off, 02=DO0 off, DO1 on, 03=DO0 on, DO1 on
SS
Safe Value, data format is same as PP
Example
:
Command : ~014
Receive : !010000
Read address 01 PowerOn/Safe Value, return PowerOn Value
is DO0 off, DO1 off, Safe Value is DO0 off, DO1 off.
Related Command
:
Sec.2.38
~AA5PPSS
Related Topic
:
Sec.3.2
Module Status,
Sec.3.3
Dual Watchdog Operation
Note
: The command is for I-7011/11D/11P/11PD only