35
I-7011, I-7018 User Manual
Rev:B1.0
2.14 $AA9(Data)
Description
: Set CJC Offset Value
Syntax
:
$AA9(Data)[CHK](cr)
$
delimiter character
AA
address of setting module (00 to FF)
9
command for setting CJC offset value
(Data)
CJC offset value comprises a sign and 4 hexadecimal
digits, from -1000 to +1000, each count is 0.01°C.
Response
:
Valid Command :
!AA[CHK](cr)
Invalid Command :
?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
!
delimiter for valid command
?
delimiter for invalid command
AA
address of response module (00 to FF)
Example
:
Command : $019+0010
Receive : !01
Set address 01 CJC offset increase 16 counts (+0.16°C), re-
turn success.
Related Command
:
Sec.2.8
$AA3