53
I-7011, I-7018 User Manual
Rev:B1.0
2.31 @AACE
Description
: Clear Event Counter
Syntax
:
@AACE[CHK](cr)
@
delimiter character
AA
address of setting module (00 to FF)
CE
command for clear event counter
Response
:
Valid Command :
!AA[CHK](cr)
Invalid Command :
?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
!
delimiter for valid command
?
delimiter for invalid command
AA
address of response module(00 to FF)
Example
:
Command : @01RE
Receive : !0101234
Read address 01 event counter, return 1234.
Command : @01CE
Receive : !01
Clear address 01 event counter, return success.
Command : @01RE
Receive : !0100000
Read address 01 event counter, return 0.
Related Command
:
Sec.2.30
@AARE
Related Topic
:
Sec.3.4
Digital Input and Event Counter
Note
: The command is for I-7011/11D/11P/11PD only