22
I-7011, I-7018 User Manual
Rev:B1.0
2.1 %AANNTTCCFF
Description
: Set module Configuration
Syntax
:
%AANNTTCCFF[CHK](cr)
%
a delimiter character
AA
address of setting module(00 to FF)
NN
new address for setting module(00 to FF)
TT
new type for setting module (Ref
Sec.1.10
)
CC
new baudrate for setting module (Ref
Sec.1.10
)
FF
new data format for setting module (Ref
Sec.1.10
)
When changing the baudrate or checksum, it is neces-
sary to short the pin INIT* to ground.
Response
: Valid Command :
!AA[CHK](cr)
Invalid Command :
?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
!
delimiter for valid command
?
delimiter for invalid command. While change baudrate
or checksum setting without shorting INIT* to ground, the
module will return invalid command.
AA
address of response module(00 to FF)
Example
:
Command :
%0102050600
Receive : !02
Change address from 01 to 02, return success.
Related Command
:
Sec.2.7
$AA2
Related Topics
:
Sec.1.10
Configuration Tables,
Sec.3.1
INIT* pin Operation