CALIBRATION
This feature is required to calibrate force monitoring levels. Screen prompts guide user through calibration. It is
generally not required to select this menu setting as the Pulse Operator will prompt for calibration upon exit from
menu, if required. If setting limits from Push Button Station, the first 2 operations will automatically calibrate the
operator. Furthermore, the Operator will continue to re-calibrate during regular operation.
NOTE: IF YOU CHANGE ANY OF THE FOLLOWING SETTINGS, THE
OPERATOR WILL PROMPT FOR RECALIBRATION WHEN EXITING THE
MENU:
Door Limits, Open Speed, Close Speed, PWM Frequency, Open
Rampdown and Close Rampdown.
THE CALIBRATION OF THE DOOR INVOLVES THE FOLLOWING STEPS:
- An automatic slow opening cycle of the door. (You will be prompted to open
the door)
- A close cycle of the door. Press the CLOSE button per prompt to Calibrate
Closing Force. If a reversing device is activated, the Operator will abort this
step and prompt you to start again.
- You will be prompted to open the door to Calibrate Opening Force.
- Calibration is complete. If you are calibrating using the Menu setting, you will
need to exit the menu before normal operation of the door can begin.
BALANCE CHECK
Once selected from the menu, the door will automatically run through one full
close/open cycle (after an encoder reset). It will then report on the screen values
representing the force required to open and to close the door. The difference in
these numbers represents the imbalance, and adjustments to the spring tension
should be made accordingly. Run this feature again to verify proper adjustment.
FACTORY RESET
This setting allows for a reset of all menu options to the factory default. These are
the Factory Settings:
STARTUP MENU
Closing Timer: .......................................................................................................................................... OFF
Door Limits Setup: .................................................................................................................................. 4 Rotations - Must be Re-Programmed by Installer
Open Speed: .......................................................................................................................................... Medium
Close Speed: .......................................................................................................................................... Medium
Opening Force: ....................................................................................................................................... 99
Closing Force: ........................................................................................................................................ 30
Open Rampdown: ................................................................................................................................. Auto
Close Rampdown: .................................................................................................................................. Auto
Open Slow Speed: .................................................................................................................................. Normal
Close Slow Speed: .................................................................................................................................. Normal
PWM Frequency: .................................................................................................................................... 12 kHz
Output Relay: ........................................................................................................................................... Energized When Open
After performing factory reset (if deemed necessary), adjust settings as required, and re-program limit settings and
perform calibration thereafter.