ICON Levelpro 300S Series Operating Manual Download Page 16

The 

Submersible Level Sensor

 is designed to operate while submerged in the actual application liquid. Avoid 

installing the level transmitter along the bottom of the tank if materials such as sludge will build up and coat/cover 
the transmitter. This also includes any debris that will settle along the bottom of the tank. In these applications, it 
is best to suspend the transmitter above the highest level of sludge/debris that will occur. See Fig A.

Note:

 Use caution when connecting the cable within the junction 

box. A ventilation/reference tube is located within the cable. The 
purpose of this tube is to provide a comparison between current 
atmospheric pressure and the pressure that is being exerted on
the sensing diaphragm within the tank.

The reference tube must be open and free to allow air to flow 
back to the pressure diaphragm.

Avoid blocking or bending the ventilation tube by compressing 
the cable.

Avoid :

 installations where other tank requirements will cause the transmitter to move or swing.

Ex:

 A mixer blade could cause the level transmitter to whip around within the tank. An alternative would be 

to move the transmitter to a more stable section of the tank or to install the Transmitter inside a still 
well/drop tube. This will minimize the effects created by the mixer.

Termination:

 The cable for the transmitter is terminated at a LP100 junction box located on top of the tank. 

Since the vent tube is contained within the cable, the pressure within the junction box. A Gortex

®

 Breather 

to ensure accurate atmospheric pressure inside the junction which is necessary as a reference to the 
pressure acting on the sensor at the bottom of the tank.

The inside of the function box must be clean, dry and free of moisture.

Position :

 The transmitter is not position sensitive.

Mounting :

 The transmitter can be mounted via several methods. It can be suspended from the cable, it 

can be placed resting on the bottom of the tank in either horizontal or vertical orientation, or it can be 
attached to a pipe or hardwired using the 

LP100

 conduit box on the top of the housing.

Location :

 Select a location where the temperature of the transmitter will be within the specification of the 

sensor.

A mixer blade could cause the level transmitter to whip around within the tank. An alternative would be to 
move the transmitter to a more stable section of the tank or to install the Transmitter inside a still well/drop 
tube. This will minimize the effects created by the mixer.

Installations where other tank requirements will cause the transmitter to move or swing.

Fig B

Fig C

PP Cord Grip

Gortex Breather

PP Cord Grip

No VaporBloc

®

VaporBloc

®

 Installed

VaporBloc

®

Vaporbloc

®

Fig A

Correction Sensor Position

For Fuming Chemicals

Vapor

Inside

No

Vapor

Vapor

Blanket

SLUDGE

www.iconprocon.com | [email protected] | 905.469.9283

16

Continuous Submersible Level Transmitter

R

300S Series

Summary of Contents for Levelpro 300S Series

Page 1: ...Submersible Level Sensors 300S Series Operating Manual Continuous Submersible Level Sensor 300S Series R www iconprocon com sales iconprocon com 905 469 9283 Diesel DEF Chemicals R...

Page 2: ...250B Display Connection Diagram Sensor TVL Display Connection Diagram Sensor Sentinel LTE TVL Display Understanding Level Measurement Application Details Getting Started Calculating Max Range of Sens...

Page 3: ...evice and should be kept nearest its location always accessible to all employees This operating manual is copyrighted The contents of this operating manual reflect the version available at the time of...

Page 4: ...after mainte nance work the probe has to be submerged slowly into the medium A rough immersion into the medium can damage or destroy the diaphragm If there is any danger of damage by lightning or ove...

Page 5: ...K 0 1 Full Scale Over One Year Response Time 10 msec Thermal Effects Offset and Span Permissible Temperatures Electrical Protection Thermal Drift 0 02 FSO K in Compensated Range 13 F 178 F 25 C 85 C S...

Page 6: ...re After Features New Vaporbloc Technology NEMA 4X Enclosure Tool Free Wiring Terminals All Plastic NEMA 4X Enclosure 2 Threaded Connection Excellent Chemical Resistance Weather Resistant Gortex Air B...

Page 7: ...Technology for Outdoor Applications No Assembly Required 8 Levels of Brightness Signal Peak Value Detection Dampens Noise 3 Wire Cord Grips Included No Add Ons Relay Lights Audible Alarm Function Comp...

Page 8: ...hrough Cable Gland Remove Heat Shrink Discard Heat Shrink Remove Filter from Vent Tube Feed Wires through VaporBloc Ensure VaporBloc is Oriented Correctly Sensor Junction Box Installation www iconproc...

Page 9: ...rBloc Installed Take Junction Box Open Lid Open Lid Fuming Liquids Please Install VaporBloc 1 Feed Sensor Red and Black Wire Breather into Junction Box 2 Tighten Cord Grip 1 4 Turn Lid is Tethered Do...

Page 10: ...Tighten Only Connection Diagram Sensor 250B Display 300S Series Level Sensor Supply Supply Vs Red Black Sensor Wire Red Terminal 1 Black Terminal 3 Red Terminal 2 Black Terminal 4 300S Series Sensor 1...

Page 11: ...ay 4 20 Output Examples Pump Shut Off Valve Shut Off Wiring to a Loop Powered Display 300S Series Level Sensors 1 2 3 4 5 6 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Power Supply 120VAC Terminal 1 2 TVL...

Page 12: ...2 3 4 5 6 Junction Box Terminals Green wire Terminal 5 Black wire Terminal 4 Junction Box Terminals Red wire Terminal 3 Black wire Terminal 2 13 12 11 10 09 08 07 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6...

Page 13: ...he Tank Empty 4mA setting 2 Full The Pressure being exerted on the sensor s diaphragm at the highest point Liquid Level within the Tank Full 20mA setting 3 Chemical Concentration Specific Gravity Temp...

Page 14: ...e sensor range changes when submersed into liquids with different Specific Gravities Please note that the physical location of the level transmitter will indicate the lowest level of measurement withi...

Page 15: ...he sensor has increased and is now 64 or 816 The liquid in Tank 2 has a S G 2 which is 2X Heavier than H20 The 34 sensor is now going to be installed into a tank to measure a liquid with a S G 2 Range...

Page 16: ...inated at a LP100 junction box located on top of the tank Since the vent tube is contained within the cable the pressure within the junction box A Gortex Breather to ensure accurate atmospheric pressu...

Page 17: ...be is fitted with a Gortex Filter this must remain attached in order to prevent moisture particulate or insects from entering Do Not Remove Avoid blocking or bending the ventilation tube The LP100 Ins...

Page 18: ...cal mechanical or chemical damage due to improper accidental or negligent use 3 Have been modified or altered 4 Anyone other than service personnel authorized by Icon have attempted to repair 5 have b...

Page 19: ......

Reviews: