The default for the Input 1 is 4 mA and this will not change.
Typically, the Empty setting will be the tank is empty (example. 000.0 Gallons, 000.0 inches, 000.0 feet etc.).
20mA typically reflects the Full setting will be when the tank is full (example: 500.0 Gallons, 120.0 inches, 10.0 feet, etc.)
Shielded cable is recommended for control loop wiring.
Use the Red wire as the (+) and the Black wire as the (-)
Wiring to the Levelpro Series Tank Level Controller
External
Display
+
+
+
4-20
Output
Examples : Pump Shut-Off
Valve Shut-Off
Wiring to a Loop Powered Display :
300S Series Level Sensors
1
2
3 4
5
6
16 15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
Power Supply 120VAC
Terminal 1 & 2
TVL Channel Terminals
TVL Series
Level Process
Display | Controller
Jumper wire
3 to 8
Contactor-Valve
Pump
Magnetic
Contactor Relay
Alarm
ProAlert-1000
Audible / Vesual
Output Relays
Output Relays
Wiring LP 100
Junction Box
Connection Diagram -
Sensor
+
TVL Display
A L
R 1
R 2
MENU
ESC
ENTER
R
A L
R 1
R 2
MENU
ESC
ENTER
R
MENU
ESC
ENTER
AL
R1
R2
R3
R4
R
www.iconprocon.com | [email protected] | 905.469.9283
11
Continuous Submersible Level Transmitter
R
300S Series