8.0 OPERATION
8.1 Parameter calibration and erasing.
To achieve best level of protection of the pump, it is essential that parameter calibration be done immediately after successful
pump installation or pump maintenance.
Setting the parameter calibration.
Pump/s must be able to pump water to enable correct calibration. If pumps are calibrated without water, overload and pump
stalled errors may occur later.
If calibration is required without water, please contact White International for advice.
Press the
MODE
key to switch to manual state. If the control panel is locked press
MODE
and
STORE
keys at the same time to
unlock and go into manual mode. Make sure that the pump is not running and LCD screen is displaying:
Press the
A START
key to run pump A, confirm the pump and all pipe network is in normal working state (including voltage,
amps etc) with LCD screen displaying:
Press the
STORE
button. The control panel makes a “beep” and
a countdown starts with the LCD displaying:
Control now counts down from 5 seconds.
The pump stops running and parameter calibration is completed with LCD displaying:
Press the
B START
key to repeat calibration for pump B.
Erasing former parameter.
When pump is reinstalled after maintenance or a new pump is installed, user must erase the former
calibration and a new calibration must be done.