2.3

 

Connections for pump over temperature protection (where supplied with pump). 

 

 

 

Note: 

to realize the pump motor winding over temperature protection, it requires that there must be over-

temperature switches embedded in the pump motor winding (microtherms as fitted to Zenit 3ph pumps 2.2 
kW or greater)

. To utilise the pump’s over temperature protection connect the pump’s microtherm leads to 

terminals 9 and 11, 10 and 12 and remove the jumper. 

Note: 

if the pump is without over temperature switch, please use jumper to connect terminals 9 and 11, 10 

and 12. 

2.4 Installing float switches and probes. 

Float switch installation. 

 

Do not encase sensor leads, float switches or signal cables in metal pipes. Use PVC or PE tubing. 

Liquid probe installation. 

 

Jumper Leads 

Summary of Contents for DPC1

Page 1: ...BIA DPC1 rev 4 Page 1 Installation and Operation Manual DPC1...

Page 2: ...er must be disconnected from the power supply 3 Do not open the cover during running the controller 4 Do not splash water or other liquid over the controller 5 Do not allow children or infirm persons...

Page 3: ...ugh float switches or probes 11 2 0a INSTALLATION DRAINAGE WITH AUTOMATIC PUMPS 2 1a Electrical connection to the power supply and pump 15 2 2a Function switch setting 16 2 3a Connections for pump ove...

Page 4: ...ply and pump 33 4 2a Function switch setting 34 4 3a Connections for pump over temperature protection where supplied 35 4 4a Installing float switches and probes 35 4 5a Diagrams for transfer by liqui...

Page 5: ...here there is the need to control and protect single pump installations managing the automatic operation by a variety of switching methods Typical usage scenarios include Stormwater Sewage Booster set...

Page 6: ...oltage 5 sec Trip response time of dry run 6 sec Recovery time of over load 30 min Recovery time of under over voltage 5 min Recovery time of dry run 30 min Trip voltage of over voltage 115 of rated i...

Page 7: ...splaying some fault information network connection error icon when this icon appears it means there is no network connections or network connection error between pump control box and SC slave controll...

Page 8: ...e operation the control panel should be disconnected from the power supply and one should wait at least 2 minutes before opening the control panel Never connect AC power to output L and N terminals En...

Page 9: ...t applications Before setting the function switch the control panel should be disconnected from the power supply After completing the setting apply power to the control panel and observe the applicati...

Page 10: ...Zenit 3ph pumps 2 2 kW or greater To utilise the pump s over temperature protection connect the pump s microtherm leads to terminals 9 and 11 10 and 12 and remove the jumper Note if the pump is withou...

Page 11: ...witches 2 5 Electrical connections for DRAINAGE applications 2 5 1 Drainage by liquid level control through float switches or probes Note for 4 float switch installation connect float switch A pump of...

Page 12: ...ugh float switches or probes cont Note for 4 float switch installation connect float switch A pump off to terminals 1 and 3 float switch B 1st pump on to terminals 1 and 5 float switch C 2nd pump on t...

Page 13: ...BIA DPC1 rev 4 Page 13 2 5 1 Drainage by liquid level control through float switches or probes cont...

Page 14: ...varies between probe 2 and probe 3 float switch A up and down 2nd pump start condition Liquid level in the sump reaches probe 4 float switch B up the control panel will run the second pump Pumps run s...

Page 15: ...r maintenance operation the control panel should be disconnected from the power supply and one should wait at least 2 minutes before opening the control panel Never connect AC power to output L and N...

Page 16: ...different applications Before setting the function switch the control panel should be disconnected from the power supply After completing the setting apply power to the control panel and observe the...

Page 17: ...Zenit 3ph pumps 2 2 kW or greater To utilise the pump s over temperature protection connect the pump s microtherm leads to terminals 9 and 11 10 and 12 and remove the jumper Note if the pump is withou...

Page 18: ...vates the high level alarm connected to the control panel the second pump will start and the alarm will activate until the high level float deactivates If a pump fail situation is detected then the pu...

Page 19: ...ontrol panel alternates power supply between pumps every 240 hours When liquid level in the sump is above the automatic pump float switch on position the pump that is being supplied power will run Ala...

Page 20: ...ce operation the control panel should be disconnected from the power supply and one should wait at least 2 minutes before opening the control panel Never connect AC power to output L and N terminals E...

Page 21: ...ent applications Before setting the function switch the control panel should be disconnected from the power supply After completing the setting apply power to the control panel and observe the applica...

Page 22: ...otection connect the pump s microtherm leads to terminals 9 and 11 10 and 12 and remove the jumper Note if the pump is without over temperature switch please use jumper to connect terminals 9 and 11 1...

Page 23: ...BIA DPC1 rev 4 Page 23 3 5 Electrical connections for BOOSTING applications 3 5 1 Water supply by pressure control through pressure switch and tank...

Page 24: ...BIA DPC1 rev 4 Page 24 3 5 1 Water supply by pressure control through pressure switch and tank cont...

Page 25: ...BIA DPC1 rev 4 Page 25 3 5 1 Water supply by pressure control through pressure switch and tank cont...

Page 26: ...ning automatically when pressure in the pipeline varies in the range of pressure switch B Extra demand Single pump is running pressure in the pipeline still decrease to the setting of pressure switch...

Page 27: ...ce operation the control panel should be disconnected from the power supply and one should wait at least 2 minutes before opening the control panel Never connect AC power to output L and N terminals E...

Page 28: ...different applications Before setting the function switch the control panel should be disconnected from the power supply After completing the setting apply power to the control panel and observe the a...

Page 29: ...otection connect the pump s microtherm leads to terminals 9 and 11 10 and 12 and remove the jumper Note if the pump is without over temperature switch please use jumper to connect terminals 9 and 11 1...

Page 30: ...BIA DPC1 rev 4 Page 30 4 5 Electrical connections for TRANSFER applications 4 5 1 Water supply by liquid level control through float switches or probes...

Page 31: ...BIA DPC1 rev 4 Page 31 4 5 1 Water supply by liquid level control through float switches or probes cont...

Page 32: ...ingle pump stops running control box will alternate double pumps running automatically when liquid level varies from Probe 1 Probe 4 Float Switch A Down level Up level Down level Extra demand when sin...

Page 33: ...or maintenance operation the control panel should be disconnected from the power supply and one should wait at least 2 minutes before opening the control panel Never connect AC power to output L and N...

Page 34: ...fferent applications Before setting the function switch the control panel should be disconnected from the power supply After completing the setting apply power to the control panel and observe the app...

Page 35: ...Zenit 3ph pumps 2 2 kW or greater To utilise the pump s over temperature protection connect the pump s microtherm leads to terminals 9 and 11 10 and 12 and remove the jumper Note if the pump is withou...

Page 36: ...y it is recommended to use float switches 4 5a Electrical connections for TRANSFER HOT WATER CIRCULATION applications 4 5 1a Hot Water Circulation with or without thermostat The control panel alternat...

Page 37: ...contact White International for advice Press the MODE key to switch to manual state If the control panel is locked press MODE and STORE keys at the same time to unlock and go into manual mode Make sur...

Page 38: ...r auto state the control panel will run or stop the pump according to the signal from the liquid level probe or float switch Note under auto state if the pump is running and user wants to stop the pum...

Page 39: ...the pump running conditions Displaying the last five failure record Press the MODE key to switch to manual state make sure the pump is not running and the LCD screen is displaying Hold pressing A STOP...

Page 40: ...by using B STOP key 5 8 Pump disable To disable a pump independently press A STOP or B STOP and MODE at the same time 6 0 Communication link The control panel has communication interface that along w...

Page 41: ...following chart shows main technical parameters of communication between the control panel and the slave controller Main technical data Physical interface RS485 Bus Interface asynchronous semi duplex...

Page 42: ...to restart the pump every calibrated running ampere pump is in 30 min until running ampere is restored to over load protection state normal pump damaged inspect pump flashing of parameter calibration...

Page 43: ...BIA DPC1 rev 4 Page 43...

Page 44: ...BIA DPC1 rev 4 Page 44...

Reviews: