[ Coolant Flow Control Valve: Checking and Adjusting Pressure ]
※ If the pressure of the coolant flow control valve is inappropriate, it may use more water or may not produce ice.
※ Please check the user manual to adjust it to appropriate pressure.
1. While the product is "OFF", connect the gauge to the high pressure nipple of the "Freezing Unit".
2. Place the power switch to "ICE" and run the product.
3. Five minutes after running, check whether the gauge pressure matches the setting (refer to product specification).
4. If the setting and gauge pressure do not match, slowly turn the "Coolant Flow Control Valve" with a tool to adjust.
(Counterclockwise: Increases Pressure,
Clockwise: Decreases Pressure)
About water supply and drain connections
After connecting the product water supply and drain, do not allow water droplets (condensate) to
fall on the floor.
Please cover it sufficiently with insulation material to prevent damage.
If water falls on the floor and causes damage, the manufacturer is not responsible.
Warning
Decrease coolant
(Decrease coolant)
Increase Coolant
(Lower Pressure)
● Changes approximately 20 psi in each revolution