NPRG 870 – NPRG 860
User’s Guide
Date : 09/2010
Edition :13/06/2017
Sheet : 4
Issue : D
2. Regulation and operation functions - Local functionalities
2.1 ANSI
Functions
Regulation of speed "NPRG 860 - NPRG 870" - ANSI 90.
Regulation of voltage “NPRG 870” - ANSI 90 + management of 4 generators.
Synchrocheck “NPRG860 - NPRG 870” - ANSI 25 + management of 4 generators.
2.2 Operation
functions NPRG 860
Calculation of the paralleling circuit breaker closing time for anticipation
Dead Busbar paralleling
Shift phase of the VT “Generator” measurements
Electrical quantities measurements :
Phase voltage U
GE
, U
BB
Frequency
F
GE
, F
BB
Difference of voltage
U (U
GE
– U
BB
)
Angular
variation
Compensated angular
variation
Variation
of
frequency
F (F
GE
– F
BB
)
Acceleration / Deceleration (Hz/s)
Paralleling CB closing time (ms)
anticipation (°)
Storage of the last 250 events and saving of the last 200 events on lack of the auxiliary
supply
Storage of four disturbance recordings, according to COMTRADE
®
standard
2.3 Operation functions NPRG 870
Idem
NPRG860
Four settings groups for the management of 4 Generators
2.4 User’s functions available
In local mode, the following functions are available:
Choice of language
Displaying of the Automatic synchroniser identification
Displaying of the paralleling values
Displaying of each memorized value: measurements
Displaying of each events recorded
Displaying the status of each inputs / Outputs
Change the setting of the disturbance pre-time
Change the settings of the Modbus
®
communication
(speed, format, …)
Adjustment of LCD contrast
NPRG860 – NPRG870 Software Version.