User’s Guide
NPM800 – NPM800R
NPM800RE
Date : 05/2013
Edition :30/01/2014
Folio : 15
Indice : g
5.2 Measurement menu (V1.24 and V2.xx firmware only)
This menu displays any real time measurement of the protection, as well as the values kept
in memory.
MAIN MENU
MEASUREMENTS
Available real time measures
CURRENT I1
0.0 A
Measure of the phase 1 primary
current
0.0 to 65535A
CURRENT I3
0.0 A
Measure of the phase 3 primary
current
0.0 to 65535A
CURRENT Io
0.00 A
Measure of the earth Io primary
current
0.0 to 65535A
FREQUENCY
50.00 Hz
Measure of the network frequency
45 to 55 if Fn = 50 Hz
55 to 65 if Fn = 60 Hz
THERMAL IMAGE
0.0 %
Measure of the thermal state of
motor
0.0 to 500 %
NEGATIVE SEQ.
0.0 %
Measure of the rate of negative
sequence of current
POSITIVE SEQ.
0.0 %
Measure of the rate of positive
sequence of current
CURRENT START
0.0 A
Maximum current measured during
last start (firmware 2.xx)
0 to 65535A
STARTS ALLOWED
4
number of authorized remaining
starts
Inactive if function MAX
NBR STARTS inactive.
START TIME
3.00 s
Duration of the last start
1 to 200 s