5.15 Communication Modbus® menu (if option available)
This menu is used to set the parameters of the Modbus® communication function: slave
number, size, speed, activity and loop tests.
MAIN MENU
COMMUNIC. MODBUS
Configuration of the Modbus RS485
communication option
V1.24 and V2.xx Firmware s
Or
MAIN MENU
RS485 COMMS
Configuration of the Modbus RS485
communication option
Since V3.00 Firmware
SLAVE NUMBER
2
Slave number of protection
1 to 255
FORMAT
8b+0p+ASCII2s
number of bits + bits of stop
+ ASCII/Binary format
Parity: 1p = pair, 1i = odd,
0p= without
p0 = forced to 0, p1 = forced
to 1
SPEED
9600 bauds
Speed transmission on RS485 link
300, 600 ,1200 ,1800, 2400,
4800, 9600, 19200 38400,
57 600,115 200 bauds
RECEPT. TIMEOUT
0.10 s
Set the time delay of reception
timeout
0.10 to 20 s
ACTIVITY TIMEOUT
0.20 s
Set the time delay of activity timeout
0.10 to 20 s
ACTIVITY TEST
Mes.Not Received
Test of the parameter setting and the
wiring of Modbus
message received / not
received: correct activity /
communication problem
5.16 Change of code menu