5.11 Remote control menu
This menu allows enabling the remote control functions, choice of the level of load-shedding,
choice of the reclose time delay assignment of the trip and reclose relays and choice of the
reclose pulse.
This menu is available if the communication option is present.
5.11.1 Telecontrol menu (V1.24 and V2.xx Firmware)
MAIN MENU
TELECONTROL
Information about remote control
option
TELECONTROL
Active
Choose Active to use remote control
option
Active or Inactive (Active if
communication available)
LOAD SHED LEVEL
6
Set the level of load-shedding.
1 to 6 (Level 6 inhibits the
load-shedding function)
RE-LOAD DELAY
20.00 s
Set the time delay before reclosing
1.00 s to 120.00 s
TRIP RELAY
A B C D
Select relay to assign to remote
control trip
See chap 4 to choose a relay
or to modify the assignment
TRIP RELAY
E F G
(D, E, F, G relay if option
available)
RECLOSE RELAY
A B C D
Select relay to assign to remote
control close order
See chap 4 to choose a relay
or to modify the assignment
RECLOSE RELAY
E F G
(D, E, F, G relay if option
available)
RECLOSE PULSE
200 ms
Setting of the minimum duration of
reclosing pulse
100 to 500 ms
O/O INPUT
Input 1
Display of input assigned to the O/O
interlock position (CB closed)
No input, Input 1 to 8 (or 1 to
4 according option)