ALARM OPERATION: 

1. 

The enclosure temperature is above or below the alarm set point

The display flashes, 

 +

+

 or 

 +

+

 icons will also flash with the display and the audible alarm 

sounds (if activated). The enclosure temperature must rise or fall by 2°F (1°C) before the alarm resets.

  

 

2. 

A fan failure is detected

The controller in the Ice Qube TMS will test its fan speeds regularly. When a fan malfunctions or its speed is over 35% 
of the set range, the controller will give a fan malfunction alarm, and the  

icons 

+

+ “fan No.” will appear on the screen. The fan numbers “1” and “2” refer to internal circulating fans; “3”, 

“4” and “5” refer to external circulating fans; and “6” refers to the hydrogen fan. The hydrogen fan option is not available 
for TEC Series. 

3. 

The filter day timer has expired

:  

The display flashes showing

, and the audible alarm sounds (if activated). The filter alarm can be cleared by 

pressing “

EXIT

”. 

Should be disabled for these models.

 

4. 

A sensor malfunction has been detected

+

+

 +“---” indicates the evaporator sensor malfunction. 

 

 

 

Summary of Contents for QD-ENG-68

Page 1: ...ments Check that cable length is sufficient to interface with power supply and thermoelectric unit 2 Route the DC power cable and controller cable exiting from the bottom of the controller to the thermoelectric unit Insert the cable connectors into the mating connector on the thermoelectric unit Check the connectors are secure 3 Insert the power cable connector shipped loose into the DC power inte...

Page 2: ... the temperature on the digital display will begin to decrease When the temperature inside the enclosure decreases 7 degrees Fahrenheit below the Cooling on set point the outside fan s will cycle off The cool air fan s will continue to operate at low speed circulating air within the enclosure The controller has a factory programmed 7 degrees Fahrenheit 4 degrees Celsius cooling differential Exampl...

Page 3: ...ack to normal mode from the controller programming mode Press the SELECT button to continue programming and icons indicate the cooling on set point is shown on the controller display The cooling system will begin operation at this temperature and will remain operating until the enclosure temperature decreases approximately seven degrees Fahrenheit four degrees Celsius below the cooling on set poin...

Page 4: ... first key is pressed on the key pad the controller display shows 1 indicating the first digit of the pin code has been entered Numbers 2 3 and 4 are displayed sequentially after pressing the other keys When the fourth digit of the pin code is entered the controller will move on to the next step of the programming If the fourth pin code is not entered within 60 seconds the system will log out auto...

Page 5: ...ions or its speed is over 35 of the set range the controller will give a fan malfunction alarm and the icons fan No will appear on the screen The fan numbers 1 and 2 refer to internal circulating fans 3 4 and 5 refer to external circulating fans and 6 refers to the hydrogen fan The hydrogen fan option is not available for TEC Series 3 The filter day timer has expired The display flashes showing an...

Reviews: