QD-ENG-68 Rev0 7/12/16 

4

Press “

SELECT

”  to  continue  the  setting.    

and   

icons appear on the screen, indicating the setting for low 

temperature alarm. The alarm will activate at this temperature and will automatically reset at two degrees Fahrenheit (or 
one degree Celsius) above this temperature.  Press the “

+

” or 

“-

” button to change the alarm setpoint within a range of -

31ºF (-35ºC) to 7º F (4ºC) below the 'heating on' set point. 

Press “

SELECT

” to continue the setting. When

and 

 appears on the screen, the display will show the temperature at 

which all fans will be running at full speed.  Press the “

+

” or “

-

“ key pads to change the high speed set point within a range 

from the ‘cooling on set point’ to 72°F (30°C) above ‘cooling on set point’. 

Press “

SELECT

” to enter the alarm function setting. The screen shows the current status of the alarm. When “off” is shown 

on the screen, all the alarm functions will stop. Press “

+

” or “

-

” to change the alarm switches accordingly. If the “OFF” mode 

is selected, no alarms will activate and the audible on/off select function is skipped. 

 

Press “

SELECT

” to enter the audible alarm setting. When 

or

is lit, “on” or “off” will appear accordingly on the LCD 

screen to show the status of the audible alarm. Press “

+

” or “

-

” to toggle the mode as desired.  

Press “

SELECT

” to enter the temperature unit setting. Press “+” or “-” to select the desired temperature unit of Fahrenheit 

or Celsius.  
 
Press “

SELECT

” to continue. T

he display shows “PIN”.

 If you need to set a new pin code, press “

+

” on the key pad. 

When “0” shows on the screen, the controller is ready to accept the new pin code. Use the keys “

+

”, “

-

”, “

SELECT

” and 

EXIT

” to reset a new 4-digit pin code. (The four keys can be set as pin code in any order). When the first key is pressed 

on the key pad, the controller display shows -1-, indicating the first digit of the pin code has been entered. Numbers -2-, -
3-, and -4- are displayed sequentially after pressing the other keys. When the fourth-digit of the pin code is entered, the 
controller will move on to the next step of the programming. If the fourth pin code is not entered within 60 seconds, the 
system will log out automatically. The pin code setting fails and the system will continue to use the previous pin code. 
 

 

*** CAUTION*** 

Always record the selection sequence (PIN code) and store in a secure place. 

Press "

SELECT

” to continue. The 

 and 

 icons are displayed and the filter maintenance reminder setting is shown. 

Press “

+

” or “

-

” to change the alarm setting. Its setting range is 0-180 days. 

Programming 0 days will disable the alarm.

 

 

NOTE:  The required number of days to set this alarm will be determined by the ambient air conditions.  The 
filter alarm should be set to “0” to disable the filter alarm for systems that do not have a filter.

 

Press “

SELECT

” to enter the communication address setting. The LCD screen is will show the current communication 

address. Press “

+

” or “

-

” to change the address value within range of 1-255. The factory setting of the communication 

address is 1. This function is not available for certain models. 

 

Programming of the controller is now complete.  Press the 

“SELECT

” button to review all of the settings.  Press the 

“EXIT

” button to enter the selected settings and to return to the normal operating mode. 

NOTE:  If “EXIT: button is not pressed, any changes to the program will NOT be saved.

 

 

Recovering the Factory Settings 

In order to recover the default factory settings in the controller, press 442213 under the normal operation condition. When 
the LCD screen shows “---” for 3 seconds, the controller restarts. Then the controller parameters are set back to factory 
default settings.  

 
 

 
 
 
 

Summary of Contents for QD-ENG-68

Page 1: ...ments Check that cable length is sufficient to interface with power supply and thermoelectric unit 2 Route the DC power cable and controller cable exiting from the bottom of the controller to the thermoelectric unit Insert the cable connectors into the mating connector on the thermoelectric unit Check the connectors are secure 3 Insert the power cable connector shipped loose into the DC power inte...

Page 2: ... the temperature on the digital display will begin to decrease When the temperature inside the enclosure decreases 7 degrees Fahrenheit below the Cooling on set point the outside fan s will cycle off The cool air fan s will continue to operate at low speed circulating air within the enclosure The controller has a factory programmed 7 degrees Fahrenheit 4 degrees Celsius cooling differential Exampl...

Page 3: ...ack to normal mode from the controller programming mode Press the SELECT button to continue programming and icons indicate the cooling on set point is shown on the controller display The cooling system will begin operation at this temperature and will remain operating until the enclosure temperature decreases approximately seven degrees Fahrenheit four degrees Celsius below the cooling on set poin...

Page 4: ... first key is pressed on the key pad the controller display shows 1 indicating the first digit of the pin code has been entered Numbers 2 3 and 4 are displayed sequentially after pressing the other keys When the fourth digit of the pin code is entered the controller will move on to the next step of the programming If the fourth pin code is not entered within 60 seconds the system will log out auto...

Page 5: ...ions or its speed is over 35 of the set range the controller will give a fan malfunction alarm and the icons fan No will appear on the screen The fan numbers 1 and 2 refer to internal circulating fans 3 4 and 5 refer to external circulating fans and 6 refers to the hydrogen fan The hydrogen fan option is not available for TEC Series 3 The filter day timer has expired The display flashes showing an...

Reviews: