PROGRAMMING THE CONTROLLER:

 

The digital controller has many function settings that may or may not be required for your application. However, the controller 
has been set at the factory with typical default settings for immediate system operation. Please review the following default 
settings. 

 

     

Cooling Start Temperature 

 

80ºF  (27°C)              

 

Heating Start Temperature 

 

50ºF  (10°C) 

      

High Temperature Alarm  

 

100ºF  (38°C) 

 

Low Temperature Alarm                    

40ºF  (4°C) 

 Full 

Speed 

Temperature 

  98ºF 

 

(37°C) 

       Visual Alarm           

       

 

“ON”                        

 

Audible Alarm        

 

 

“ON”     

 

Default Temperature Unit  

 

Fahrenheit 

 

User Pin code Setting   

 

 “+”  “–“ “Select” “Exit”  (1,2,3,4) 

 Filter 

Maintenance 

Alarm  0 

days-disabled 

 Communication 

Address 

  1 

(not 

used)

To change the controller settings, please follow the sequence below to enter the pin code 1234 into the program modification:   

                                                   

 

“+” 

 

 

 

“-” 

 

   2 

“Select” 

  3 

“Exit”  

 

 

 
 

 
Figure

 

2: Digital Tap Sensitive Controller 

 

 
After entering the above sequence, three alternating flashing boxes should be shown on the display face, indicating the 
code was accepted.  If no selection is made within one minute, the system returns to the normal operating mode. 

NOTE: 

If entering the PIN code fails the first time, please wait until the key icon

disappears and then enter the pin code again.  

Press “Exit” to go back to normal mode from the controller programming mode. 

Press the “

SELECT” 

button to continue programming.   and 

 icons indicate the 'cooling on' set point is shown on the 

controller display. The cooling system will begin operation at this temperature and will remain operating until the enclosure 
temperature decreases approximately seven degrees Fahrenheit (four degrees Celsius) below the cooling on set point. 
Press the 

“+”

 or “

-” 

button until the desired set point is displayed.  The range for this adjustment is 70° to 126°F, (21° to 

52°C). 

Press the “

SELECT”

 button to continue programming.  When 

 and 

is displayed on the screen, it indicates the 'heating 

on' setting. The heating system will begin operation at this temperature and remain operating until the enclosure temperature 
increases approximately seven degrees Fahrenheit (four degrees Celsius) above the 'heating on' set point.  Press the “

+

” 

or “

-

” until the desired set point is displayed within a range of -22°F to 68°F (-30°C to +20°C). 

NOTE: Review alarm settings if the ‘cool on’ or ‘heat on’ set points have been changed. 

Press “

SELECT

” to continue programming. 

 and

 icons appearing on the screen indicate the setting for high 

temperature alarm set point. 

The alarm will activate at this temperature and will automatically reset at two 

degrees Fahrenheit (one degree Celsius) below this temperature.  Press the “

+”

 or “

-”

 button to change the 

alarm set point within a range of 7ºF (or 4ºC) above the 'cooling on' set point, to 140°F (60°C).

 

Summary of Contents for QD-ENG-68

Page 1: ...ments Check that cable length is sufficient to interface with power supply and thermoelectric unit 2 Route the DC power cable and controller cable exiting from the bottom of the controller to the thermoelectric unit Insert the cable connectors into the mating connector on the thermoelectric unit Check the connectors are secure 3 Insert the power cable connector shipped loose into the DC power inte...

Page 2: ... the temperature on the digital display will begin to decrease When the temperature inside the enclosure decreases 7 degrees Fahrenheit below the Cooling on set point the outside fan s will cycle off The cool air fan s will continue to operate at low speed circulating air within the enclosure The controller has a factory programmed 7 degrees Fahrenheit 4 degrees Celsius cooling differential Exampl...

Page 3: ...ack to normal mode from the controller programming mode Press the SELECT button to continue programming and icons indicate the cooling on set point is shown on the controller display The cooling system will begin operation at this temperature and will remain operating until the enclosure temperature decreases approximately seven degrees Fahrenheit four degrees Celsius below the cooling on set poin...

Page 4: ... first key is pressed on the key pad the controller display shows 1 indicating the first digit of the pin code has been entered Numbers 2 3 and 4 are displayed sequentially after pressing the other keys When the fourth digit of the pin code is entered the controller will move on to the next step of the programming If the fourth pin code is not entered within 60 seconds the system will log out auto...

Page 5: ...ions or its speed is over 35 of the set range the controller will give a fan malfunction alarm and the icons fan No will appear on the screen The fan numbers 1 and 2 refer to internal circulating fans 3 4 and 5 refer to external circulating fans and 6 refers to the hydrogen fan The hydrogen fan option is not available for TEC Series 3 The filter day timer has expired The display flashes showing an...

Reviews: