background image

Due to ICE AIR’s ongoing product development programs, the information in this document is subject to change without notice.

7

Commercial Water Loop Application

Commercial systems typically include a number of units connected 
to a common piping system. Any system or unit piping maintenance 
work can introduce air into the piping system. Therefore, air 
elimination equipment is a major portion of the mechanical room 
plumbing. In piping systems expected to utilize water temperatures 
below 60°, 1/2” closed-cell insulation is required on all piping 
surfaces to eliminate condensation. Metal-to-plastic threaded joints 
should never be used due to their tendency to leak over time.

Balancing valves, flow control valves, motorized solenoid valves and 
variable speed pumping systems may also be used.

The piping system should be flushed to remove dirt, pipe shavings, 
chips, and other foreign material prior to operation (refer to “System 
Cleaning and Flushing” section). The flow rate is usually set between 
2.25 and 3.5 GPM per ton of cooling for most applications of water 
loop heat pumps. To ensure proper maintenance and servicing, P/T 
ports are imperative for temperature and flow verification, as well as 
performance checks.

Water loop heat pump (cooling tower/boiler) systems typically utilize 
a common loop, maintained between 60 - 90°F. The use of a closed 
circuit evaporative cooling tower with a secondary heat exchanger 
between the tower and the water loop is recommended. If an open 
type cooling tower is used continuously, chemical treatment and 
filtering will be necessary.

System Start

System Cleaning and Flushing

Cleaning and flushing the unit is the most important step to ensure 
proper start-up and continued efficient operation of the system. 
Follow the instructions below to properly clean and flush the system:

1.  Verify that electrical power to the unit is OFF.

2.  Verify that supply and return riser service valves are closed at 

each unit.

3.  Fill the system with water, leaving the air vents open. Bleed all air 

from the system, but do not allow the system to over flow. Check 
the system for leaks and make any required repairs.

4.  Adjust the water and air level in the expansion tank.

5.  With strainers in place, start the pumps. Systematically check 

each vent to ensure that all of the air is bled from the system.

6.  Verify that make-up water is available and adjusted to properly 

replace any space remaining when all air is purged. Check the 
system for leaks and make any additional repairs if needed.

7.  Set the boiler to raise the loop temperature to approximately 

85°F (29.4°C). Open the drain at the lowest point in the system. 
Verify that make-up water replacement rate equals rate of bleed. 
Continue to bleed the system until the water appears clean or for 
at least three hours, whichever is longer.

8.  Completely drain the system.

Summary of Contents for 5CHPW09

Page 1: ...CHPW Slope or Flat Top Console Unit Water Source Heat Pump WSHP Unit ELA 8842 Installation Manual ...

Page 2: ...se to install or service heating and air conditioning equipment WARNING HIGH VOLTAGE Disconnect all power before servicing or installing unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death To ensure that the unit operates safely and efficiently it must be installed according to these installation instructions and all local codes and ordina...

Page 3: ...against the Bill of Lading Ensure all components are intact upon delivery and free from damage Note any damage on the delivering carrier s Bill of Lading 2 The ICE AIR unit s arrive prefabricated with an enclosure Ensure both the unit and the enclosure are properly attached 3 Make sure the floor is level in both directions so the unit s airflow will be aligned Confirm adequate drainage is availabl...

Page 4: ... amperage of the dedicated electrical service to the unit is correct and the unit can reach the power supply 6 Position the unit so the air filter can be removed easily and required maintenance can be performed without interference 7 A minimum obstructed distance of 36 should be kept around the unit IMPORTANT To avoid permanent damage to the unit DO NOT operate during construction in an open space...

Page 5: ...s and field installer removes the plugs on the field piping side Water piping terminates in the same location regardless of the connection and valve options Filter Installation Each unit is delivered with a filter for the filter rack which can be found at the bottom of the unit as shown below In order to install the filter slide the piece horizontally into the slot Ensure the filter is effectively...

Page 6: ...ction is made by connecting the incoming line voltage wires to the terminal block Volt Operation All commercial units are factory wired for specific voltages These include 115 VAC 208 230 VAC 265 277 VAC For 230 volt single phase operation the primary voltage to the transformer must be changed NOTE Failure to change the primary voltage lead when using 230 VAC line voltage may result in electrical ...

Page 7: ...ween 60 90 F The use of a closed circuit evaporative cooling tower with a secondary heat exchanger between the tower and the water loop is recommended If an open type cooling tower is used continuously chemical treatment and filtering will be necessary System Start System Cleaning and Flushing Cleaning and flushing the unit is the most important step to ensure proper start up and continued efficie...

Page 8: ... Pan and Drain Hoses Check the unit condensate drain pan and drain hoses annually to ensure proper condensate drainage If any foreign matter build up in the drain pan is found clean the drain pan and drain hoses frequency of cleaning depends on the level of dirt and pollutants that may be present in the indoor environment Evaporator Coil Check and clean if necessary the unit evaporator coil annual...

Page 9: ...OGNIZE THIS SYMBOL AS A SAFETY PRECAUTION WARNING ICE AIR will not be responsible for any injury or property damage arising from improper service or service procedures If you install or perform service on this unit you assume responsibility for any personal injury or property damage which may result Many jurisdictions require a license to install or service heating and air conditioning equipment W...

Page 10: ...e Heat limit setting is 51 F to 91 F Operation Normal Mode 1 Press ON OFF to turn on thermostat 2 Press MODE to change the system mode 3 There are three operation modes Cool mode Heat mode Auto mode Cool Mode 1 To activate Cool mode press the MODE button until COOL displays 2 Press UP DOWN arrow buttons to your desired temperature 3 Compressor will cycle when temperature reaches the set point Afte...

Page 11: ...usted 4 In Auto mode Heat set point will be set first and press UP or DOWN to set the Heat set point Press FAN to confirm the Heat set point Cool set point will be set second and press UP or DOWN to set the Cool set point 5 Permanent Override will be canceled if user changes the operation mode or turns off the unit 6 Hold FAN button 5 seconds to cancel the Permanent Override mode Set Day and Time ...

Page 12: ...n speed is manually selected the fan will continue to blow Heating Cycle Set the thermostat for Heating If applicable the motorized valve opens as long as the thermostat calls for Heating This sends a 24 volt signal to the terminal to the compressor contactor and the compressor starts At the same time a 24 volt signal flows through the fan relay and the blower starts in HIGH speed if the unit is i...

Page 13: ... system failures complete the following checks and data entries before the system is put into full operation Temperatures Circle F or C Antifreeze __________Type __________ Pressures Circle PSIG or kPa Allow unit to run 15 minutes in each mode before taking data Do not connect service manifold gauges during start up unless instructed by ICE AIR service tech Cooling Mode Heating Mode Return Air Tem...

Page 14: ...ping Orientation LH Return R Piping Orientation RH Return U Piping Orientation Universal Allows For Field Conn On Either Side X Piping Orientation Not Applicable Item Matrix Name Code String Value Description 12 WIRE WHIPS A Wall mounted with 6 5 foot wire whip B Wall mounted with 10 foot wire whip C Wall mounted with 12 foot wire whip D Wall mounted with 30 foot wire whip E Wall mounted with 50 f...

Page 15: ...S M Manual Air Vent T Bleed Tee X No Air Vents 21 VALVE PACKAGE ASSEMBLED OR SHIPPED LOOSE A Assembled S Shipped Loose X None 22 SECONDARY DRAIN PANS G Power Coated Galvanized Steel Secondary Drain Pan S Stainless Steel Secondary Drain Pan P Plastic Secondary Drain Pan X No Secondary Drain Pan 23 SECONDARY OVERFLOW SWITCH E Electronic Secondary Overflow Switch X No Secondary Overflow Switch 24 SEC...

Page 16: ...bligation beyond the terms of these express warranties or to state that the performance of the product is other than that published by Ice Air General Conditions The above warranties are void if Ice Air s equipment has been damaged misused subjected to abnormal use or service or its serial number has been altered defaced or removed or payment for the equipment is in default Ice Air is not responsi...

Reviews: