- Setup of EXT-MODULE SENSOR alarm level and high/low value in [PROTECTION].
Items
Alarm Level
Delay
Time
Sequence Applied
Not
use
Warning
Trip
Stop
Shutdown
USER TEMP 2
HIGH
○
○
○
○
○
2[s]
BUILD-UP ~
COOLDOWN
User Temperature 2 detected higher than set value
USER TEMP 2
LOW
○
○
○
○
○
2[s]
BUILD-UP ~
COOLDOWN
User Temperature 2 detected lower than set value
USER TEMP 2
SENSOR
◎
5[s]
Always
User Temperature 2 Sensor not connected
COOLANT TEMP
LH HIGH
○
○
○
○
○
2[s]
BUILD-UP ~
COOLDOWN
Left Coolant Temperature detected higher than value
COOLANT TEMP
LH LOW
○
○
○
○
○
2[s]
BUILD-UP ~
COOLDOWN
Left Coolant Temperature detected lower than set value
COOLANT TEMP
LH SENS
◎
5[s]
Always
Left Coolant Temperature Sensor not connected
COOLANT TEMP
RH HIGH
○
○
○
○
○
2[s]
BUILD-UP ~
COOLDOWN
Right Coolant Temperature detected higher than set value
COOLANT TEMP
RH LOW
○
○
○
○
○
2[s]
BUILD-UP ~
COOLDOWN
Right Coolant Temperature detected lower than set value
COOLANT TEMP
RH SENS
◎
5[s]
Always
Right Coolant Temperature Sensor not connected
OIL PRESS LH
HIGH
○
○
○
○
○
2[s]
BUILD-UP ~
COOLDOWN
Left Oil Pressure Value detected higher than set value
OIL PRESS LH
LOW
○
○
○
○
○
2[s]
BUILD-UP ~
COOLDOWN
Left Oil Pressure Value detected lower than set value
OIL PRESS LH
SENSOR
◎
5[s]
Always
Left Oil Pressure Sensor not connected
OIL PRESS RH
HIGH
○
○
○
○
○
2[s]
BUILD-UP ~
COOLDOWN
Right Oil Pressure detected higher than set value
OIL PRESS RH
LOW
○
○
○
○
○
2[s]
BUILD-UP ~
COOLDOWN
Right Oil Pressure Value detected lower than set value
OIL PRESS RH
SENSOR
◎
5[s]
Always
Right Oil Pressure Sensor not connected
USER PRESS 1
HIGH
○
○
○
○
○
2[s]
BUILD-UP ~
COOLDOWN
User Temperature 1 detected higher than set value