REV. N
NeoGCP
i7
PLUS+
- 32 -
- VDO Press Sensor Setup
Resistance
10
31
52
71
88
107
140
184
Press
0
10
20
30
40
50
70
100
9. DI-CONFIG
- Digital Input(DI) Setup.
- When signal of user set type(N/O, N/C) is input, set message(TEXT) will output after set delay time(0.0
~ 25.0) and then running mode of Gen-set will switch according to Alarm Level(7 level).
- Setup possible in Stop mode. (Some menus excluded)
Item
DI List
(SET)
Description
TYPE
DELAY
ALARM
Fault
Contact
USER FAULT
User fault contact
[N/O]
[N/C]
0.0~25.0 [s]
Total 7
levels
USER FAULT
(RUN)
User fault contact
(Running)
USER FAULT
(STOP)
User fault contact
(Stop)
EM’CY STOP S/W
Emergency stop
COOLANT TEMP S/W Coolant temp switch
OIL PRESS S/W
Oil press switch
COOLANT LEVEL
S/W
Coolant level switch
NO CHARGING S/W
Charge failure
FAIL TO START
Start failure
FAIL TO STOP
Stop failure
BUILD-UP EXPIRE
Fail to Build-up
OVER SPEED
Over speed
OCGR
Ground over current
Status
Contact
BREAKER AUX
Breaker auxiliary
Impossible
Impossible
UVR SIGNAL
UVR run
FIRE-RUN
Emergency run
BLOCK MODE
Block mode
MANUAL MODE
Manual mode
AUTO MODE
Auto mode
GEN START
Gen-set start
GEN STOP
Gen-set stop
BREAKER CLOSE
Breaker close
BREAKER OPEN
Breaker open
ALARM RESET
Alarm reset
IDLE STATUS
IDLE run
GEN VOLTAGE
CHANGE
Voltage change by
generator wiring
BUZZER STOP
Stop buzzer operation
USER TIMER INPUT
On / Off delay signal
0~999.9[s]