- When contact is input, Gen-set will start and when contact is not input, Gen-set will stop.
- Setup : TYPE(N/O, N/C),
Menus that are influenced
Setup
Description
[CONTROL] → [MAINS SENSING]
[UVR Contact] User set DI port
[CONTROL] → [MAINS SENSING]] → [AUTO-
START DELAY]
0~7200 [s]
Start delay time in [AUTO]
mode
[CONTROL] → [MAINS SENSING]→ [AUTO-
START VOLTAGE]
0~6600 [Vac]
Start voltage in [AUTO]
mode.
[CONTROL] → [MAINS SENSING] → [AUTO-
STOP DELAY]
0~7200 [s]
Stop delay time in [AUTO]
mode
[CONTROL] → [MAINS SENSING]→ [AUTO-
STOP VOLTAGE]
0~6600 [Vac]
Stop Voltage in [AUTO]
mode
FIRE-RUN
9.16.
- Used as emergency-run contact.
- When contact is input, operation status will switch to [FIRE] mode, and after 5[s] of [PRE-CRANK] delay
time, Gen-set will start.
- Operation status will be same as [AUTO] mode.
- Setup : TYPE(N/O, N/C),
BLOCK
9.17.
- Used as block mode contact.
- When contact is input, operation status will switch to [BLOCK] mode.
- Setup : TYPE(N/O, N/C),
MANUAL
9.18.
- Used as manual mode contact.
- When contact is input, operation status will switch to [MANUAL] mode.
- Setup : TYPE(N/O, N/C),
AUTO
9.19.
- Used as auto mode contact.
- When contact is input, operation status will switch to [AUTO] mode.
- Setup : TYPE(N/O, N/C),