REV. N
NeoGCP
i7
PLUS+
- 47 -
SVR DELAY
SVR
Waiting time for RPM to fall within rated
range
0 ~ 60 [s]
COOLDOWN TIME
COOLDOWN Setup cooldown time in AUTO Mode
0 ~ 600 [s]
STOP-HOLD TIME
STOP
Stop signal holding time
5 ~ 30 [s]
A/H INPUT TYPE
TYPE
[C_AIR HEATER] setup of use/not use and
operation method
Not use,
sensor, switch,
switch
A/H OPERATED
TEMP
TEMP
[C_AIR HEATER] output in temp lower than
set value
0 ~ 150 [℃]
A/H OPERATED
TIME
TIME
[C_AIR HEATER] output holding time
0 ~ 7200 [s]
12. PROTECTION
- Setup of Protection during Running or Stop.
- Setup impossible during running.
- In case of OVR, OCR, and OCGR, Constant and Inverse will operate at the same time.
Duplicate operation in Instant setup.
Items
Description
Setup
OVR
CONSTANT
Start from over voltage
level
0.5 ~ 20.0 [s]
INVERSE
Start from over voltage
level
Refer to Inverse Characteristics
Curve
INSTANT
Start from 130% of rated
voltage
Within 200ms
(The higher the input voltage, time
will decrease)
OCR
CONSTANT
Start from over current
level
0.5 ~ 20.0 [s]
INVERSE
Start from over current
level
Refer to Inverse Characteristics
Curve
SET
Start from 200% of rated
current
Within 200ms
(The higher the input current, time
will decrease)
OCGR
CONSTANT
Start from ground over
current level
0.5 ~ 20.0 [s]
INVERSE
Start from ground over
current level
Refer to Inverse Characteristics
Curve
SET
Start from 200% of ground
current level
Within 200ms
(The higher the input current, time
will decrease)