ICAR by ORTEA NEXT
ALL75 mar19
16 / 40
NOA = Alarm normally de-energized. The relay is energized when any alarm with the
Global alarm
property arises.
NCA = Alarm normally energized. The relay is de-energized when any alarm with the
Global alarm
property arises.
FAN = The relay controls the cooling fan.
MAN = Relay is energized when device is in MAN mode.
AUT = Relay is energized when device is in AUT mode.
A01 ... A12= The relay is energized when the alarm specified is active.
P.19
Setpoint (target value) of the cos
. Used for standard applications.
P.20
Language of scrolling alarm messages
12.2
ADVANCED MENU
COD
DESCRIPTION
PSW
UoM
DEF
RANGE
P.21
Password enable
Adv
OFF
OFF / ON
P.22
User password
Usr
001
0-999
P.23
Advanced password
Adv
002(*)
0-999
P.24
Wiring type
Usr
3PH
3PH Trifase / 1PH Monofase
P.25
Step trimming
Adv
ON
ON Abilitato / OFF Disabilitato
P.26
Setpoint cle
Usr
0.00
0 – 0.10
P.27
Setpoint clearance -
Usr
0.00
0 – 0.10
P.28
Step insertion mode
Usr
STD
STD Standard / LIN Lineare / DISC
P.29
Cogeneration cos
setpoint
Usr
OFF
OFF / 0.50 IND – 0.50 CAP
P.30
Disconnection sensitivity
Usr
sec
OFF
OFF / 1 – 600
P.31
Step disconnection passing in MAN
Usr
OFF
OFF
Disabilitato / ON Abilitato
P.32
Capacitor current overload alarm threshold
Adv
%
50
OFF / 0...150
P.33
Capacitor overload immediate disconnection threshold
Adv
%
83
OFF / 0.. 200
P.34
VT primary
Usr
V
OFF
OFF / 50-50000
P.35
VT secondary
Usr
V
100
50-500
P.36
Temperature UoM
Usr
°C
°C °Celsius / °F Fahrenheit
P.37
Fan start temperature
Adv
°
25
0 ... 212
P.38
Fan stop temperature
Adv
°
20
0 ... 212
P.39
Temperature alarm threshold
Adv
°
55
0 ... 212
P.41
Maximum voltage alarm threshold
Adv
%
110
OFF / 90...150
P.42
Minimum voltage alarm threshold
Adv
%
90
OFF / 60...110
P.43
THD V alarm threshold
Adv
%
6
OFF / 1...250
P.44
THD I alarm threshold
Adv
%
12
OFF / 1...250
P.45
Maintenance interval
Adv
h
9000
8760(**)
1 - 30000
P.46
Bar-graph function
Usr
Kvar ins/tot
Kvar ins/tot / Corr att/nom / Delta kvar att/tot
P.47
Default auxiliary measure
Usr
TPF sett.
Delta kvar / V / A / TPF settimanale / THDC /
Temp / THDV / THDI / ROT
P.48
Backlight flashing on alarm
Usr
OFF
OFF / ON
P.49
Serial node address
Usr
01
01-255
P.50
Serial speed
Usr
bps
9.6k
1.2k / 2.4k / 4.8k / 9.6k / 19.2k / 38.4k
P.51
Data format
Usr
8 bit – n
8 bit, no parity
8 bit, odd / 8bit, even
7 bit, odd / 7 bit, even
P.52
Stop bits
Usr
1
1-2
P.53
Protocol
Usr
Modbus RTU
Modbus RTU / Modbus ASCII
P.54
Number of insertions for maintenance
Adv
kcnt
OFF
OFF / 1…60
P.21
If set to OFF, password management is disabled and anyone has access to the settings and commands menu.
P.22
With P.21 enabled, this is the value to specify for activating user level access. See Password access chapter.
P.23
As for P.22, with reference to Advanced level access. (*) Available value only if the controller is not installed on the ICAR cabinet
P.24
Number of phases of the power correction panel.
P.25
Enables the measurement of the actual power of the step, performed each time they are switched in. The measure is calculated, as the current
measurement is referred to the whole load of the plant. The measured power of the steps is adjusted (trimmed) after each switching and is
displayed on the step life statistic page. When this function is enabled, a 15 sec pause is inserted between the switching of one step and the
following, necessary to measure the reactive power variation.
P.26 – P.27 Tolerance around the setpoint. When the cos
is within the range delimited by these parameters, in AUT mode the device does not connect /
disconnect steps even if the delta-kvar is greater than the smallest step
P.28
Selecting mode of steps insertion.
Standard mode - Normal operation with free selection of the steps
Linear mode - the steps are connected in progression from left towards right only following the step number and according to the LIFO (Last In First
Out) logic. The controller will not connect a step when the system steps are of different ratings and by connecting the next step, the set-point value
would be exceeded.
Disc -
As in the Standard mode but with reduced time spent in capacitive
P.29
Setpoint used when the system is generating active power to the supplier (with negative active power / power factor ).
P.30
Disconnection sensitivity. Same as the previous parameter but related to disconnection. If set to OFF the disconnection has the same reaction time
of connection set with the previous parameter.
P.31
If set to ON, when switching from AUT mode to MAN mode, steps are disconnected in sequence.
P.32
Capacitors overload protection Trip threshold (alarm A07), that will arise after an integral delay time, inversely proportional to the overload value.
Note: You can use this protection only if the capacitors are not equipped with filtering devices such as inductors or similar.
P.33
Threshold beyond which the integral delay for tripping of the overload alarm is zeroed, causing the immediate intervention of the
A08
alarm.
P.34 – P.35 Data of VTs eventually used in the wiring diagrams.
P.36
Unit of measure for temperature.
P.37 – P.38 Start and stop temperature for the cooling fan of the panel, expressed in the unit set by P.36. The cooling fan is started when the temperature is
>= to P.37 and it is stopped when it is < than P.38.
P.39
Threshold for generation of alarm
A08 Panel temperature too high
.
P.41
Maximum voltage alarm threshold, referred to the rated voltage set with P.07, beyond which the alarm
A06 Voltage too high
is generated.
P.42
Undervoltage alarm threshold, referred to the rated voltage set with P.07, below which the alarm
A05 voltage too low
is generated.
P.43
Maximum installation voltage THD alarm threshold, beyond which the alarm
A10 THDV too high
is generated.
P.44
Maximum installation current THD alarm threshold beyond which the alarm
A05 voltage too low
is generated.