PARAMETER SETTING (SETUP) VIA THE FRONT PANEL
To access the programming menu (setup): To enter parameter programming the unit must be in TEST mode (first
programming)
or in MAN mode
From the normal measurement display, press and hold
for 3 seconds to recall the main menu.
SET
is displayed on
the main display.
If the password has been set (P.21 = ON), the display shows
PAS
(password entry request instead of
SET
). Set the numeric
password using
▲ ▼
and then press
to move to next digit. If the password is correct the unit will show
OK U
or
OK A
depending on the entered password is user or the advanced level. The password can be defined with parameters P.22 and
P.23. Factory default is 001 and 002 respectively. If the entered password is wrong the unit will show
ERR
. After having
entered the password, the access is enabled until the unit is re-initialized or for 2 minutes without pressing any key. After
having entered the password, repeat the procedure to access the parameter setting.
Press
▲▼
to select the desired submenu (
BAS
ADV
ALA
... ) that is shown on the alphanumeric display.
The following table lists the available submenus:
COD
DESCRIPTION
BAS
Access to Base menu
ADV
Accesso to Advanced menu
ALA
Accesso to Alarm menu
CMD
Access to Command menu
CUS
Access to Custom menu
EXIT
Exits saving modifications.
SAVE
Exits without saving (cancel)
Press
to access the submenu. When in a submenu, the main display shows the code of the selected parameter (eg
P.01), while the numeric/alphanumeric displays at the bottom of the screen shows the parameter value and / or
description. Press
to advance in the selection of items (such as scroll through parameters P.01
P02
P03… ), or
press
to go back to the previous parameter. While a parameter is selected, its value can be increased or decreased
with
▲ ▼
.
Once the last parameter of the menu has been reached, pressing
once more will return back to the
submenu selection.
Using
▲▼
, select
SAVE
to save the changes or
EXIT
to cancel
.
Alternatively, from within the programming, holding
for three seconds will save the changes and exit directly. If the user
does not press any key for more than 2 minutes, the system leaves the setup automatically and goes back to normal viewing
without saving the changes done on parameters (like EXIT). N.B.: a backup copy of the setup data (settings that can be
modified using the keyboard) can be saved in the eeprom memory of the RPC 5LGA regulator. This data can be restored
Firmware
revision
Model variat
Total number
of steps
TEST mode
indication
MAN mode
Connected
steps
Manual step selection
enabled
Tot kvar
inserted