Power supply
1×230V +6%/-10%
,
50Hz
,
PE
Motor protection
There is no need for additional motor protection
Protection rating
IP 44
Insulation class
F
Maximum relative humidity
≤ 95%
Maximum pressure in the central heating system
1 MPa
Minimum inflow pressure at suction depending on
heating medium temperature
Medium
temperature
Minimum
inflow pressure
≤ 85
o
C
0.005 MPa
≤ 90
o
C
0.028 MPa
≤ 95
o
C
0.050 MPa
Acoustic pressure of working pump
43 dB (A)
Permissible ambient temperature
0
~
+40
℃
Maximum heating medium temperature
TF95
Maximum heating up of pump surface
≤ 110
℃
Range of temperatures of pumped liquid
2
~
+95
℃
a.
Installation dimensions
7.
TROUBLESHOOTING
Warning:
Before any maintenance or repair activities, make sure that the power supply is cut off and
cannot be turned on by accident.
Issue:
Possible cause:
Solution:
The pump fails to launch
Tripped installation fuse
Check the cause, replace the fuse
Overcurrent circuit breaker switched off
Start the breaker
Pump damaged
Replace the pump
Voltage too low
Check if the main voltage
is compliant with the supplier's
specification
Pump rotor blocked
Unlock the rotor
Loud system operation
Air in the installation
Vent the installation
Flow too high
Decrease the inflow pressure at
the pump inlet
Loud pump operation
Air in the pump
Vent it
Inflow pressure too low - cavitation
Increase the inflow pressure at the inlet to
the
pump
Heat insufficiency in the installation
Pump parameters too low
If possible, increase the pump operation
mode into a more efficient one,
otherwise
install stronger pump
Moc
silnika [W]
Model
Wymiary [mm]
L2
L1
B1
H1
H2
G
22
PSI 20-40
65
130
95
130,1
28
1”
PSI 25-40
65
130
95
130,1
28
11/2”
90
180
95
130,1
28
PSI 32-40
90
180
95
130,1
28
2”
32
PSI 20-50
65
130
95
130,1
28
1”
PSI 25-50
65
130
95
130,1
28
11/2”
90
180
95
130,1
28
PSI 32-50
90
180
95
130,1
28
2”
45
PSI 20-60
65
130
95
130,1
28
1”
PSI 25-60
65
130
95
130,1
28
11/2”
90
180
95
130,1
28
PSI 32-60
90
180
95
130,1
28
2”