3.
Because the XIV system acts as a TCP server for iSCSI connections, packets are
always routed through the Ethernet port from which the iSCSI connection was
initiated. The default gateways are required only if the hosts are not on the
same layer-2 subnet as the XIV system.
4.
If present, Ethernet VLANs and IP routers must be configured to enable
connectivity between the host systems and the XIV system.
5.
If present, IP routers must be configured to enable access between the hosts
and the XIV system.
Important:
Link aggregation is not supported. Ports cannot be bonded.
For supported interoperability configurations, see the System Storage
Interoperation Center website (www.ibm.com/systems/support/storage/config/
ssic).
Redundant configuration
In this configuration, each interface module is connected through two ports to two
different Gigabit Ethernet switches, and each host system is connected to the two
Gigabit Ethernet switches. Full connectivity is maintained in the event of a
component failure.
This configuration is the same as the redundant configuration options for Fibre
Channel networks.
For the best performance, use a dedicated iSCSI network infrastructure.
Single-switch configuration
In this configuration, a single Gigabit Ethernet switch interconnects all host
systems and interface modules.
Use non-redundant configurations only when the risks of a single point of failure
are acceptable, which is typically the case for test and development environments.
Single-port host configuration
In this configuration, a single Gigabit Ethernet switch connects to each host system
and to two interface modules.
Use non-redundant configurations only when the risks of a single point of failure
are acceptable, which is typically the case for test and development environments.
Network cable requirements
The customer is responsible for supplying cables that connect to the patch panel,
including host attachment (Fibre Channel or iSCSI) cables, management cables,
maintenance cables, and virtual private network (VPN) cables.
Table 35. Required cable types
Cables
Required cable type
Fibre Channel
50 µm (micrometer) multimode Fibre Channel cables with
LC/LC or LC/SC connectors
Note:
If you require 62.5-µm fibers, contact an IBM service
representative for assistance.
Chapter 7. Network and host connectivity requirements
59
Summary of Contents for XIV Gen3 Series
Page 6: ...vi IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 8: ...viii IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 10: ...x IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 16: ...xvi IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 24: ...xxiv IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 52: ...28 IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 88: ...64 IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 94: ...70 IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 116: ...92 IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 125: ......
Page 126: ...IBM Printed in USA SC27 5412 09...