Lay hoses side-by-side as they run between the heat exchanger and the pump unit
manifold, and allow the hoses to freely move. Leave enough slack in the hoses
below the rear door so that no pressure is exerted on the mated couplings when
the hoses are connected and operating. When you route hoses, avoid sharp bends
that cause hose kinks and avoid hose contact with sharp edges.
Non-raised floor hose requirements and management
In data centers without a raised floor, straight hose assemblies cannot make the
sharp bend to exit between the floor and the rack door without kinking the hose.
Hose assemblies with right-angle metal elbows are needed to route the hoses along
the floor. Make the 90° turn upwards within the gap between the bottom of the
heat exchanger and the floor surface, and then connect to the heat exchanger
couplings (see Figure 31 on page 88).
Front of rack
(viewed from top)
Door
xiv10134
Figure 30. Raised floor and non-raised floor hose management example 2: loop under the
rack with door open
Chapter 10. Planning for the rear-door heat exchanger
87
Summary of Contents for XIV Gen3 Series
Page 6: ...vi IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 8: ...viii IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 10: ...x IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 16: ...xvi IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 24: ...xxiv IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 52: ...28 IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 88: ...64 IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 94: ...70 IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 116: ...92 IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 125: ......
Page 126: ...IBM Printed in USA SC27 5412 09...