![background image](http://html1.mh-extra.com/html/ibm/xiv-gen3-series/xiv-gen3-series_planning-manual_4145274062.webp)
Table 21. Power consumption
Number of modules
in the rack
Number of disk
drives
Model 281x-114 with
SSDs in kVA High
performance (1 and 2
TB / 3 TB)
Model 281x-214 with
SSDs in kVA High
performance (2 TB /
3 TB / 4 TB / 6 TB)
Model 281x-314 with
SSDs in kVA High
performance (4 TB /
6 TB)
6
72
2.9 / 2.9
2.5 / 2.6 / 2.6 / 2.6
N/A
9
108
4.3 / 4.2
3.6 / 3.8 / 3.9 / 3.9
4.7 / 4.7
10
120
4.7 / 4.7
4.0 / 4.2 / 4.3 / 4.3
5.1 / 5.1
11
132
5.1 / 5.2
4.3 / 4.5 / 4.6 / 4.6
5.5 / 5.5
12
144
5.5 / 5.7
4.7 / 4.9 / 5.0 /5.0
6.0 / 6.0
13
156
5.9 / 6.1
5.0 / 5.3 / 5.4 / 5.4
6.5 / 6.5
14
168
6.5 / 6.7
5.5 / 5.7 / 5.8 / 5.8
7.0 / 7.0
15
180
6.9 / 7.2
5.8 / 6.1 / 6.2 / 6.2
7.5 / 7.5
Input voltages and frequencies
This information lists the voltages or frequencies that are accepted by the IBM XIV
Storage System.
Table 22 provides the voltages and frequencies that are accepted by the XIV
system. For more information, see “Leakage current” on page xiii.
Table 22. Input voltages and frequencies
Characteristics
Voltage or frequency
Nominal input voltages
200, 220, or 240 V ac
Maximum input current
30 A or 60 A
Minimum input voltage
180 V ac
Maximum input voltage
264 V ac
Maximum ground-leakage current
0.3 A
Steady-state input frequencies
50±3 Hz or 60±3 Hz
Power line disturbance (PLD) input
frequencies
50±3 Hz or 60±3 Hz
Main-power cables specifications
Plan for power cable, connector, and receptacle requirements.
The XIV systems are available in multiple main-power cable configurations. The
automatic transfer switch (ATS) is chosen based on the required main-power
cables.
Attention:
The regional designations are general. The ATS assigned to the
regional designation might not be accurate for your country. If the input voltage
for the country uses a wye circuit, use the appropriate ATS and main-power cables
for EMEA (Europe, Middle East, and Africa) and Asia/Pacific. If input voltage for
the country uses a delta circuit, use the appropriate ATS and main-power cables
for United States, Canada, Latin America. For more information about electric
currents for various countries, see the International Trade Administration website
(http://www.trade.gov/mas/ian/ecw/all.html).
38
IBM XIV Gen3 281x-11x, 281x-21x, and 281x-314 Planning Guide
Summary of Contents for XIV Gen3 Series
Page 6: ...vi IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 8: ...viii IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 10: ...x IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 16: ...xvi IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 24: ...xxiv IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 52: ...28 IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 88: ...64 IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 94: ...70 IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 116: ...92 IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Page 125: ......
Page 126: ...IBM Printed in USA SC27 5412 09...