Chapter 1. General description
7
1.2.4 Power requirements
All Power 595 configurations are designed with a fully redundant power system. To take full
advantage of the power subsystem redundancy and reliability features, each of the two power
cords should be connected to different distribution panels.
Table 1-7 lists the electrical and thermal characteristics for the Power 595 server.
Table 1-7 Power 595 electrical and thermal characteristics
Table 1-8 on page 8 lists the electrical characteristics for 4.2 GHz and 5.0 GHz Power 595
servers, and the Powered Expansion Rack (U.S., Canada, and Japan).
Maximum wet bulb
23 degrees C (73 degrees F) (operating)
Sound power
Declared A-weighted sound power level, per
ISO 9296: 9.2 bels (with slim line doors)
Declared A-weighted sound power level, per
ISO 9296: 8.2 bels (with acoustical doors)
Sound pressure
Declared A-weighted one-meter sound
pressure level, per ISO 9296: 79 decibels (with
slim line doors)
Declared A-weighted one-meter sound
pressure level, per ISO 9296: 69 decibels (with
acoustical doors)
a. The maximum temperatures of 32°C (90°F) and 28°C (82°F) are linearly derated above 1295
m (4250 ft).
Description
Range
Description
Range
Operating voltages
3-phase V ac at 50/60 Hz): 200 to 240 V;
380 to 415 V; 480 V
Rated current (A per phase): 48 A or 63
A or 80 A; 34 A or 43 A; 24 A or 34 A
Power consumption: 27,500 watts
(maximum for full CEC, three I/O
drawers)
Power source loading: 27.7 kVA
Thermal output: 27,500 joules/sec
(93,840 Btu/hr) maximum
Inrush current
134
Power Factor
0.99
Operating frequency
50/60 plus or minus 0.5 Hz
Maximum Power (Fully configured 4.2 GHz system)
23.3 KW
Maximum Power (Fully configured 5.0 GHz system)
28.3 KW
Maximum thermal output (4.2 GHz processor)
74.4 KBTU/hr
Maximum thermal output (5.0 GHz processor)
83.6 KBTU/hr