Chapter 1. General description
9
1.3 Minimum configuration requirements
This section discusses the minimum configuration requirements for the Power 595. Also
provided are the appropriate feature codes for each system component. The IBM
configuration tool also identifies the feature code for each component in your system
configuration. Table 1-10 on page 10 identifies the required components for a minimum
9119-FHA configuration.
Recommend
circuit breaker
rating
60 A
80 A
40 A
40 A
Cord size
6 AWG
6 AWG
8 AWG
8 AWG
Recommended
receptacle
Not specified
Electrician
installed
Not specified
Electrician
installed
Not specified
Electrician
installed
Not specified
Electrician
installed
5.0 GHz server
System rating
48 A
80 A
34 A
43 A
Plug rating
no plug
no plug
no plug
no plug
Recommend
circuit breaker
rating
60 A
100 A
40 A
63 A
Cord size
6 AWG
4 AWG
8 AWG
6 AWG
Recommended
receptacle
Not specified
Electrician
installed
Not specified
Electrician
installed
Not specified
Electrician
installed
Not specified
Electrician
installed
Powered Expansion Rack
System rating
Powered I/O
Rack
48 A
63 A
34 A
34 A
Plug rating
no plug
no plug
no plug
no plug
Recommend
circuit breaker
rating
60 A
80 A
40 A
40 A
Cord size
6 AWG
6 AWG
8 AWG
8 AWG
Recommended
receptacle
Not specified
Electrician
installed
Not specified
Electrician
installed
Not specified
Electrician
installed
Not specified
Electrician
installed
Description
World Trade
Note:
Throughout this chapter, all feature codes are referenced as #
xxxx
, where
xxxx
is
the appropriate feature code number of the particular item.
Summary of Contents for Power 595
Page 2: ......
Page 120: ...108 IBM Power 595 Technical Overview and Introduction...
Page 182: ...170 IBM Power 595 Technical Overview and Introduction...
Page 186: ...174 IBM Power 595 Technical Overview and Introduction...
Page 187: ......