• The rack must have a safe electrical distribution system. It must provide overcurrent protection for the
enclosure and must not be overloaded by the total number of enclosures installed. The electrical power
consumption rating that is shown on the nameplate should be observed.
• The electrical distribution system must provide a reliable ground for each enclosure in the rack.
Power requirements for each power supply (two per enclosure)
Ensure that your environment meets the following power requirements.
To aid in power and cooling requirements planning, Table 6 on page 30 lists the rating of each power
supply unit (PSU) by enclosure.
The power that is used by the system depends on various factors, including the number of enclosures and
drives in the system and the ambient temperature.
Table 6. Power specifications per power supply
Model and type
PSU
Input power
requirements
Maximum input
current
Maximum power
output
Elastic Storage System
3000
2000 W (2)
200 V to 240 V
single phase AC
At a frequency of
50 Hz or 60 Hz
IEC C14
standardized
10A (x2)
2000 W
The power and thermal measurements that are shown in Table 7 on page 30 were obtained in the
specific operating environment.
Table 7. Power consumption examples per enclosure
Model and type
Configuration
Total power
consumption
Caloric value (BTU/hr)
Elastic Storage System 3000
5141-AF8
1 enclosure with up to
24 dual port NVMe
drives, 3 host adapters
1632 W
5570
Note: These measurements are presented as an example. Measurements that are obtained in other
operating environments might vary. Conduct your own testing to determine specific measurements for
your environment.
Each Elastic Storage System 3000 enclosure contains two PSUs for redundancy. The total power
consumption values represent the total power that is drawn by both PSUs.
Environmental requirements
System airflow is from the front to the rear of each enclosure:
• Airflow passes between drive carriers and through each enclosure.
• The combined power and cooling module exhausts air from the rear of each canister.
Ensure that your environment falls within the ranges that are listed in the Table 8 on page 31.
30 IBM Elastic Storage System 3000: Hardware Planning and Installation Guide
Summary of Contents for ESS 3000
Page 5: ...Glossary 83 Index 91 Index 91 v...
Page 6: ...vi...
Page 10: ...x...
Page 70: ...58 IBM Elastic Storage System 3000 Hardware Planning and Installation Guide...
Page 74: ...62 IBM Elastic Storage System 3000 Hardware Planning and Installation Guide...
Page 82: ...70 IBM Elastic Storage System 3000 Hardware Planning and Installation Guide...
Page 90: ...78 IBM Elastic Storage System 3000 Hardware Planning and Installation Guide...
Page 92: ...80 IBM Elastic Storage System 3000 Hardware Planning and Installation Guide...
Page 102: ...90 IBM Elastic Storage System 3000 Hardware Planning and Installation Guide...
Page 107: ......
Page 108: ...IBM Product Number 5765 DME 5765 DAE SC28 3107 01...