To set the shutdown times for each load segment, complete the following steps:
1. From the main menu, press the down (
) button to scroll to the
Configuration
menu, and press the OK button.
2. Press the down (
) button to scroll to
Automatic on Battery Shutdown
, and
press the OK button.
3. Press the down (
) button to select the load segment that you want to set and
press the OK button.
4. Press the down (
) button to select the shutdown delay for the load segment.
5. Press the OK button for 1 second to confirm.
6. Repeat step 3 to step 5 to set the other load segment, if applicable.
Configuring battery settings
Configure the UPS settings for an installed extended battery module, including
whether to run automatic battery tests.
Configuring the UPS for an extended battery module
If the UPS is not configured for the extended battery module, the UPS reports less
battery time remaining on the UPS front panel and to any remote software. You
might receive a shutdown warning prematurely.
Conversely, if the UPS is configured for the extended battery module but the
extended battery module is not connected to the UPS, the UPS reports more
battery time remaining, and it might shut down before it issues a warning.
Note:
The default configuration is to issue an alarm when the batteries reach their
lowest limit, which enables an orderly shutdown.
For the maximum battery runtime when you are using power management software,
complete the following steps to configure the UPS for the extended battery module:
1. From the main menu, press the down (
) button to scroll to the
Configuration
menu, and press the OK button.
2. Press the down (
) button to scroll to
External Battery Modules
, and press the
OK button.
3. Press the down (
) button to select the battery number value that you want.
Configuration
Setting
UPS only (internal batteries)
0 (default)
UPS and one extended battery module
1
Note:
Runtime is automatically adjusted according to present load levels and
whether an extended battery module is configured.
4. Press the OK button for 1 second to confirm.
Chapter 3. Operating the uninterruptible power supply
29
Summary of Contents for 6000 VA LCD 4U
Page 2: ......
Page 14: ...xii 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Page 32: ...18 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Page 60: ...46 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Page 70: ...56 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Page 74: ...60 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Page 82: ...68 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Page 86: ...72 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Page 87: ......
Page 88: ...Part Number 81Y1032 Printed in USA 1P P N 81Y1032...