Table 6. Dimensions for doors (continued)
Door model
Width
Height
Depth
Weight
FC ECRC and
ECRD acoustic
front and rear
doors, black OEM
590 mm (23.2
in.)
1942 mm (76.5 in.)
110 mm (4.3 in)
17.7 kg (39 lb)
Table 7. Dimensions for side covers
Width
1
Depth
Height
Weight
2
12 mm (0.5 in.)
1070 mm (42.1 in.)
1942 mm (76.5 in.)
20 kg (44 lb)
1
Side covers increase the overall width of the rack by 12 mm (0.5 in.) per side, but are only used on the ends of
the rows.
2
Weight is for each side cover.
Table 8. Environment requirements
1
Environment
Recommended operating Allowable operating
Nonoperating
ASHRAE class
A3
Airflow direction
Front-to-back
Temperature
2
18°C - 27°C (64°F - 80°F) 5°C - 40°C (41°F - 104°F) 1°C - 60°C (34°F - 140°F)
Humidity range
5.5°C (42°F) dew point
(DP) to 60% relative
humidity (RH) and 15°C
(59°F) dew point
-12.0°C (10.4°F) DP and
8% - 80% RH
8% - 80% RH
Maximum dew point
24°C (75°F)
27°C (80°F)
Maximum operating
altitude
3050 m (10000 ft)
Shipping temperature
-40°C - 60°C (-40°F -
140°F)
Shipping relative humidity
5% - 100%
1. The final ASHRAE class is determined by the hardware that is installed in the rack. Individual specifications
for each piece of hardware must be reviewed.
2. Derate maximum allowable dry-bulb temperature 1°C per 175 m above 950 m. IBM recommends a
temperature range of 18°C - 27°C (64°F - 80.6°F).
Table 9. Service clearances
Front
1
Back
915 mm (36 in.)
915 mm (36 in.)
1
Storage racks require larger service clearances in the front of the rack.
Rear door heat exchanger
Specifications for Power orderable feature code (FC) EC05 (rear door heat exchanger indicator, model
1164-95X).
Chapter 3. Planning for hardware 27
Summary of Contents for 6.1.8.2
Page 8: ...viii...
Page 20: ...xx IBM Storage Scale System Utility Node Hardware Planning and Installation Guide...
Page 90: ...70 IBM Storage Scale System Utility Node Hardware Planning and Installation Guide...
Page 96: ...76 IBM Storage Scale System Utility Node Hardware Planning and Installation Guide...
Page 100: ...80 IBM Storage Scale System Utility Node Hardware Planning and Installation Guide...
Page 102: ...82 IBM Storage Scale System Utility Node Hardware Planning and Installation Guide...
Page 110: ...90 IBM Storage Scale System Utility Node Hardware Planning and Installation Guide...
Page 112: ...92 IBM Storage Scale System Utility Node Hardware Planning and Installation Guide...
Page 113: ......
Page 114: ...IBM Product Number 5765 DME 5765 DAE SC28 3469 00...