16
N
OTE
: S
ETTINGS ARE MADE THROUGH THE SUPPLIED
P
OWER
C
HUTE SOFTWARE OR
THE NETWORK INTERFACE CONNECTION
. R
EFER TO THE SOFTWARE HELP GUIDES FOR DETAILS
.
F
UNCTION
F
ACTORY
D
EFAULT
U
SER
S
ELECTABLE
C
HOICES
D
ESCRIPTION
High Transfer Point
100V:
108VAC
110V:
117VAC
120V:
127VAC
127V:
135VAC
200V:
216VAC
208V:
225VAC
220V:
242VAC
230V:
253VAC
240V:
264VAC
100V:
108, 110, 112, 114VAC
110V:
117, 119, 121, 123VAC
120V:
127, 130, 133, 136VAC
127V:
135, 138, 141, 144VAC
200V:
216, 220, 224, 228VAC
208V:
225, 229, 233, 237VAC
220V:
242, 246, 250, 254VAC
230V:
253, 257, 261, 265VAC
240V:
264, 268, 272, 276VAC
If the utility voltage is usually high and the
connected equipment is specified to operate
with input voltages this high, set the high
transfer point higher to avoid unnecessary
battery usage.
Low Transfer Point
100V:
92VAC
110V:
97VAC
120V:
106VAC
127V:
112VAC
200V:
184VAC
208V:
182VAC
220V:
199VAC
230V:
208VAC
240V:
217VAC
100V:
92, 90, 88, 86VAC
110V:
97, 95, 93, 91VAC
120V:
106, 103, 100, 97VAC
127V:
112, 109, 106, 103VAC
200V:
184, 180, 176, 172VAC
208V:
182, 178, 174, 170VAC
220V:
199, 195, 191, 187VAC
230V:
208, 204, 200, 196VAC
240V:
217, 213, 209, 205VAC
If the utility voltage is usually low and the
connected equipment is specified to operate
with input voltages this low, set the low
transfer point lower.