IBM 1500VA LCD 2U Rack Uninterruptible Power Supply for IBM System x
5
Specifications
Table 3 lists the specifications for the two 1500 VA UPS models.
Table 3. Specifications
Specification
IBM 1500VA LCD 2U Rack UPS
(100V/120V)
IBM 1500VA LCD 2U Rack UPS
(230V)
IBM part number
5395-1AX
5395-1KX
VA/Watts rating
1440 VA/1000W (120V)
1200 VA/1000W (100/110V)
1500 VA/1000W
Nominal output voltage (Vac)
100/120V AC
230V AC
Load groups
Two
Two
Output connections
Four NEMA 5-15R (load group 1)
Two IEC 320 C13 (load group 2)
Four IEC 320 C13 (two in each load
group)
Nominal output voltage regulation
92-108V (100V)
100-121V (110V)
106-132V (120V)
208-253V (230V)
Input
Nominal input voltage
(auto sensing at first power-up)
100/120V
220, 230, 240V; user-configurable
Input frequency (auto sensing)
50/60 Hz +/- 3 Hz
50/60 Hz +/- 3 Hz
Input connection type
IEC 320-C14
IEC 320-C14
Input cords
(1) IEC 320 C13 to NEMA 5-15P, 4.3
m
(2) IEC 320 C13 to LP-71, 4.3 m
(Taiwan)
Optional Country Specific Line Cords
(See Table 2)
Input voltage range, mains
operations
84-121V for 100V
97-145V for 120V
160V-286V for 230V
Batteries
Typical backup times
See Table 4
See Table 4
Battery type
Valve Regulated Lead Acid (VRLA) – maintenance-free, sealed, leak-proof
Optional External Battery Pack
No
No
Typical recharge time
4 hours to 90% charge from a UPS/battery discharge of 50% rated load