5. If the error persists, test the LWCO. Go to
>
SIM Menu
>
LWCO Test
> Run the test
to check if the low water cutoff sensor is opening.
10.8 Resetting a boiler after a hi-limit temperature
lockout
A boiler that has been placed in a lockout condition due to a hi-limit temperature error will need to
be reset in the controller's SIM module.
1. Go to
>
Clear Errors
>
Yes
.
2. Check that there is no air trapped in the system.
3. To reset the SIM Module, go to
>
SIM Menu
>
Hi-Limit Test
>
Reset
>
Yes
.
4. Run the boiler to ensure that the error has been cleared.
5. If the error persists, perform a hi-limit test. Go to
>
SIM Menu
>
Hi-Limit Test
> Run
the test to see if the hi-limit switch is opening. You can also perform this test for gasket
blowouts.
86
Section: Troubleshooting