2. (If applicable) Tap
System Options
> Tap the number value in the
Minimum Output
field
and enter a higher minimum output (e.g., if the minimum output is currently 10, enter 15) >
OK
>
Save
.
3. (If applicable) Tap the number value in the
Maximum Output
field and enter a lower
maximum output (e.g., if the maximum output is currently 85, enter 80) >
OK
>
Save
.
9.6 Adjusting the space heating temperature
Ensure that a reset heating or set point load is set up in the controller. See
.
To adjust the space heating temperature in:
A Reset Heating load, go to
>
Advanced Setup
> Select the
Reset Heating
load >
tap
Design supply
temperature number value (default 125° F) > On the number pad choose
a value between 50° F and 190° F >
OK
>
Save
.
A Set Point load, go to
>
Advanced Setup
> Select the
Set Point
load > tap
Boiler
Supply
temperature value > On the number pad, choose a value between 59° F and 185° F
>
OK
>
Save
.The load pump must provide adequate water flow if the boiler pump is set to
OFF.
9.7 Adjusting the domestic hot water temperature
To adjust the domestic hot water temperature, go to
>
Advanced Setup
> Select the
DHW
Tank setpoint
temperature value > On the number pad, choose a number >
OK
>
Save
.
9.8 Checking the water flow in the boiler
To check the water flow in the boiler, go to
>
Boiler Status
>
Flow Rate
. Refer to the
Specifications table in the
Installation and Operation instructions
manual for the required flow rate.
9.9 Setting overrides
Note
Date and time must be set in the boiler for overrides to work. For instructions, see
Changing and updating date and time on page 76
72
Section: Other operating procedures
Summary of Contents for V-10
Page 1: ...V 10 TOUCHSCREEN CONTROLLER MANUAL VX SERIES...
Page 40: ...Intentionally left empty...
Page 50: ...Intentionally left empty...
Page 66: ...Intentionally left empty...
Page 97: ...Wiring diagram Opt Out DHW Figure 22 Opt Out DHW wiring diagram 95 Wiring diagram Opt Out DHW...
Page 102: ......