2.8.3 Wiring single-stage heating
with boiler or combi boiler, and
single-stage cooling
Required if the boiler or the combi boiler does not have control of the pump.
Optional: 'G' for fan-only operation and 'C' for t-stat common.
Dry contact from the air handler to the boiler or combi boiler that enables a call for heat.
Required: sensors for cooling applications are available separately at IBC A/C sensor
package
.
Figure 38
Single-stage heating with boiler or combi boiler, and single-stage cooling wiring
Settings in the IBCconnect app
1. Tap
(menu icon), and select
Basic Settings
.
2. Set
Heat Mode
to
1 Stage Heat
.
3. Set
Cool Mode
to
1 Stage Cool
.
4. Set
Boiler Heating
to
Boiler Only
.
5. Set
Tankless Mode
to
On
.
6. Tap
(SAVE).
39
2.8.3 Wiring single-stage heating with boiler or combi boiler, and single-stage cooling