2.3 Duct work
Ducting design and installation should adhere to
SMACNA and/or ASHRAE guidelines. Install
the ducting system to NFPA 90B (latest edition).
Adhere to the following:
Size the supply air plenum duct fitting to
the size of the appliance's supply air
opening, and extend for 3' above the
appliance.
Size the supply and return air ducting
according to ASHRAE standards or
equivalent.
Seal all joints and connections to prevent
air leakage from the ducting system.
Choose accessories that will not
excessively restrict the air flow and
create excessive pressure drop on the
system.
Note
When using medium and high velocity systems, ensure proper duct design for optimal
system performance and noise levels.
2.3.1 Sizing the ducts
The tables below provide examples of conventional duct types and sizing for the AHU appliance
running at low velocity. If using flex / insulated flex ducting, ensure that you allow for a higher
pressure drop.
Branch Duct - CFM at 0.25"wc external static pressure (galvanized duct)
Round
CFM range
3"
20-30
4"
30-35
5"
55-65
6"
90-100
7"
135-160
Table 6
Sizing round galvanized duct for CFM range
26
Section: Installation
Summary of Contents for AHU 800
Page 44: ...5 Set Tankless Mode to Off 6 Tap SAVE 42 Section Installation...
Page 53: ...5 Set Tankless Mode to On 6 Tap SAVE 51...
Page 55: ...5 Set Tankless Mode to On 6 Tap SAVE 53...
Page 57: ...7 Set FA Damper Open T F to lowest Fresh Air temperature 8 Tap SAVE 55...
Page 58: ...This page is intentionally left blank...
Page 60: ...This page is intentionally left blank...
Page 74: ...This page is intentionally left blank...
Page 88: ...7 Air handling appliance parts diagram 86 Section Air handling appliance parts diagram...
Page 90: ...88 Section Air handling appliance parts diagram...