Heating capacity
AHU 800 - Heating Capacity (Entering Dry Bulb Temperature 70°F) @ 800 CFM
Entering Water Temperature
3 GPM
4 GPM
5 GPM
195°F (90°C)
68.6 MBH
73.2 MBH
76.2 MBH
190°F (88°C)
65.7 MBH
70.2 MBH
73.0 MBH
180°F (82°C)
60.0 MBH
64.1 MBH
66.8 MBH
170°F (77°C)
54.4 MBH
58.1 MBH
60.5 MBH
160°F (71°C)
48.7 MBH
52.1 MBH
54.3 MBH
150°F (66°C)
43.1 MBH
46.2 MBH
48.1 MBH
140°F (60°C)
37.6 MBH
40.2 MBH
41.9 MBH
130°F (54°C)
32.0 MBH
34.3 MBH
35.8 MBH
120°F (49°C)
26.5 MBH
28.5 MBH
29.7 MBH
110°F (43°C)
21.1 MBH
22.6 MBH
23.7 MBH
Table 1
Heating Capacity rating at 800 scfm (standard cubic feet / minute) - AHU 800
AHU 1200 & AHU 1200 LV - Heating Capacity (Entering Dry Bulb Temperature 70°F) @
1200 CFM
Entering Water
Temperature
3 GPM
4 GPM
5 GPM
195°F (90°C)
81.3 MBH
87.7 MBH
91.8 MBH
190°F (88°C)
78.0 MBH
84.1 MBH
88.1 MBH
180°F (82°C)
71.3 MBH
76.9 MBH
80.6 MBH
170°F (77°C)
64.6 MBH
69.8 MBH
73.1 MBH
160°F (71°C)
58.0 MBH
62.6 MBH
65.6 MBH
150°F (66°C)
51.4 MBH
55.5 MBH
58.2 MBH
140°F (60°C)
44.8 MBH
48.4 MBH
50.8 MBH
130°F (54°C)
38.3 MBH
41.4 MBH
43.4 MBH
120°F (49°C)
31.8 MBH
34.3 MBH
36.0 MBH
110°F (43°C)
25.3 MBH
27.4 MBH
28.7 MBH
Table 2
Heating Capacity rating at 1200 scfm (standard cubic feet / minute) - AHU 1200
8
Section: Specifications
Summary of Contents for AHU 800
Page 44: ...5 Set Tankless Mode to Off 6 Tap SAVE 42 Section Installation...
Page 53: ...5 Set Tankless Mode to On 6 Tap SAVE 51...
Page 55: ...5 Set Tankless Mode to On 6 Tap SAVE 53...
Page 57: ...7 Set FA Damper Open T F to lowest Fresh Air temperature 8 Tap SAVE 55...
Page 58: ...This page is intentionally left blank...
Page 60: ...This page is intentionally left blank...
Page 74: ...This page is intentionally left blank...
Page 88: ...7 Air handling appliance parts diagram 86 Section Air handling appliance parts diagram...
Page 90: ...88 Section Air handling appliance parts diagram...