AHU 1600 - Heating Capacity (Entering Dry Bulb Temperature 70°F) @ 1600 CFM
Entering Water Temperature
3 GPM
4 GPM
5 GPM
195°F (90°C)
96.9 MBH
106.7 MBH
113.2 MBH
190°F (88°C)
92.9 MBH
102.3 MBH
108.6 MBH
180°F (82°C)
84.9 MBH
93.5 MBH
99.3 MBH
170°F (77°C)
77.0 MBH
84.8 MBH
90.0 MBH
160°F (71°C)
69.1 MBH
76.1 MBH
80.8 MBH
150°F (66°C)
61.2 MBH
67.4 MBH
71.6 MBH
140°F (60°C)
53.3 MBH
58.8 MBH
62.5 MBH
130°F (54°C)
45.5 MBH
50.2 MBH
53.4 MBH
120°F (49°C)
37.7 MBH
41.6 MBH
44.3 MBH
110°F (43°C)
30.0 MBH
33.2 MBH
35.3 MBH
Table 3
Heating Capacity rating at 1600 scfm (standard cubic feet / minute) - AHU 1600
AHU 2000 LV - Heating Capacity (Entering Dry Bulb Temperature 70°F) @ 2000 CFM
Entering Water Temperature
3 GPM
4 GPM
5 GPM
195°F (90°C)
105.2 MBH
117.4 MBH
125.8 MBH
190°F (88°C)
100.8 MBH
112.5 MBH
120.6 MBH
180°F (82°C)
92.1 MBH
102.9 MBH
110.3 MBH
170°F (77°C)
83.5 MBH
93.2 MBH
100.0 MBH
160°F (71°C)
74.9 MBH
83.6 MBH
89.7 MBH
150°F (66°C)
66.3 MBH
74.1 MBH
79.5 MBH
140°F (60°C)
57.8 MBH
64.6 MBH
69.3 MBH
130°F (54°C)
49.3 MBH
55.1 MBH
59.1 MBH
120°F (49°C)
40.9 MBH
45.7 MBH
49.1 MBH
110°F (43°C)
32.5 MBH
36.4 MBH
39.1 MBH
Table 4
Heating Capacity rating at 2000 scfm (standard cubic feet / minute) - AHU 2000
9
Heating capacity
Summary of Contents for AHU 800
Page 44: ...5 Set Tankless Mode to Off 6 Tap SAVE 42 Section Installation...
Page 53: ...5 Set Tankless Mode to On 6 Tap SAVE 51...
Page 55: ...5 Set Tankless Mode to On 6 Tap SAVE 53...
Page 57: ...7 Set FA Damper Open T F to lowest Fresh Air temperature 8 Tap SAVE 55...
Page 58: ...This page is intentionally left blank...
Page 60: ...This page is intentionally left blank...
Page 74: ...This page is intentionally left blank...
Page 88: ...7 Air handling appliance parts diagram 86 Section Air handling appliance parts diagram...
Page 90: ...88 Section Air handling appliance parts diagram...