background image

IBC Technologies Inc. 

36 

VFC 15-150 and VFC 45-225 

3.1 

PRIOR TO START-UP 

a)

 

Ensure venting system is complete 
and seal tested. Confirm any 
common venting system at the 
installation site is isolated and 
independent of the VFC boiler, that 
any holes left from removal of a 
previous boiler have been sealed, 
and that any resizing of the old flue 
has been done. Fill condensation 
trap to full 7” (min) neck height for 
VFC 15-150 or 28” for VFC 45-
225.  

b)

 

Check water piping system is fully 
flushed and charged, and that all 
air has been discharged through 
loosened bleed caps. Note it is 
possible to switch all pumps on/off 
from the keypad – without a call 
for heat. This greatly simplifies 
system filling and air bleeding (go 
to 

Installer Setup

, drop down to 

Pump Purge

 and toggle to 

On

When complete, return to 

Off

, or 

this will automatically occur with a 
call for heat). Use a minimum 
water pressure of 12 psig. And 
confirm pressure relief valve is 
installed and safely drained.  

c)

 

Perform a final check of electrical 
wiring. 

3.1.1  Test Ignition Safety Shutoff  

With the boiler in operation, test the 
ignition system safety shutoff device by 
shutting the manual gas valve immediately 
outside the boiler case.  Ensure boiler has 
shut off and the appropriate Error 
information is displayed on the LCD 
screen.  To restart boiler, reset power. 

3.2 

GAS VALVE ADJUSTMENT  

The VFC modulating boilers are factory 
calibrated to operate with natural gas (or 
propane if so ordered) at sea level. The 
relevant valve adjustment screws have 
been factory sealed using Loctite thread-
lock compound, which can be broken 
where required. However,

 no mixture 

adjustment shall be performed unless 
done by a qualified technician using 
properly functioning combustion 
analyzing equipment.

 

Upon initial set up, the installer can 
enter the site elevation to compensate 
for altitude.

 Without such intervention, 

the gas valve will automatically de-rate the 
maximum input in accordance with the 
density altitude, at approximately 2% per 
1,000' above sea level. The gas valve's 
zero govenor will ensure that the gas:air 
mixture is not affected at altitude.  

To verify the proper operation of the gas 
valve in the field, the following procedure 
can be carried out by a qualified technican 
(refer to Figure 12): 

1.

 

with a small (1/8" or 3 mm) flat 
screwdriver, open the manifold 
pressure test port by turning its centre- 
screw 1 full turn counterclockwise. 
Attach a manometer between the 
manifold pressure test port and the 
reference line. 

2.

 

Allow the boiler to ignite / run against 
a large load, to maintain high fire 

3.

 

With the boiler at maximum output, 
use a 2 mm hex key to adjust the zero-
offset (see Fig.12, #9) as required to 
achieve 0" wc.  This adjustment is 
only necessary if this screw has been 
tampered with. 

4.

 

With a combustion analyzer probe in 
the flue gas, turn the Gas:Air Ratio 
Adjustment screw (Fig.12, #11) to 

Summary of Contents for VFC 15-150

Page 1: ...he vicinity of this or any other appliance Should overheating occur or the gas supply fails to shut off do not turn off or disconnect the electrical supply to the pump Instead shut off the gas supply...

Page 2: ...p 24 2 4 4 Advanced Diagnostics 24 2 4 5 Passwords 24 2 5 SEQUENCE OF OPERATION 25 2 5 1 Standby 25 2 5 2 Purging 25 2 5 3 Ignition 25 2 5 4 Heating 26 2 5 5 Circulating 26 2 5 6 Error Mode 27 2 6 OTH...

Page 3: ...viding a great degree of installation flexibility The installer must clearly indicate the vent category for the installation on the rating plate using an indelible marker See section 1 4 Venting Figur...

Page 4: ...rocarbons can reduce the life of a boiler Cleaners bleaches air fresheners refrigerants aerosol propellants dry cleaning fluids de greasers and paint removers all contain vapours which can form corros...

Page 5: ...between the installation instructions below and the code requirements the more stringent shall apply DO NOT COMMON VENT THE VFC MODULATING SERIES BOILERS WITH ANY OTHER EXISTING OR NEW APPLIANCE IMPOR...

Page 6: ...from the indoor air surrounding the boiler Provided the maximum overall vent length limit is not exceeded the installer may choose to vent the boiler through the wall directly through the roof or upwa...

Page 7: ...o be used to adapt to the appropriate diameter see Vent Travel below Exhaust venting is to be connected directly to the 2 NPT male threaded stainless steel fitting on the bottom of the pressure vessel...

Page 8: ...as the for 2 option If the site requires a horizontal exit immediately below the boiler bush out to 2 or 3 pipe in the downward vertical run immediately below the 2 threaded adaptor and elbow to horiz...

Page 9: ...ust be piped to within 1 of a drain or be connected to a condensate pump Drainage line must slope down to the drain at a pitch of per foot so condensate runs towards the trap Use the supplied vent kit...

Page 10: ...e elevation as the exhaust as shown lower down roof is OK To promote the projection of exhaust away from the building and from the intake pipe reduction of 3 pipe to 2 is permitted for a maximum linea...

Page 11: ...nless steel or plastic mesh is useful to guard against foreign objects Figure 4 Sidewall Vent Termination Piping Configuration To promote the projection of exhaust away from the building and from the...

Page 12: ...corner see CSA B149 H Clearance to each side of centreline extended above meter regulator assembly 3 0 91m within a height of 15 4 6m above the meter regulator I Clearance to service regulator vent o...

Page 13: ...t edition or applicable provisions of the local building codes in Canada in compliance with B149 The following lists are recommendations for buildings of energy saving construction fully caulked and w...

Page 14: ...S piping ensures adequate flow and de couples T issues boiler vs distribution Aim for a 20 to 30 F T across the heat exchanger at high fire there is a boiler protection throttle fence limiting the T t...

Page 15: ...dividual zones in a heating system have loads under 5 000 Btu hr the system will still benefit through use of a buffer tank to ensure a controlled supply temperature and to prevent short cycling Buffe...

Page 16: ...ping configuration requires an extra pump The VFC modulating series boilers controller hosts wiring terminals and integral relays to simplify installation and operation of this preferred layout offset...

Page 17: ...n from hot to cool loads a manually set 3 way mixing valve can be placed at the entrance to the cool load This will permit immediate circulation of mixed flow into the cool loop See separate publicati...

Page 18: ...gher head pump at a higher cost An imbalance in the head between the loads may call for a balancing valve on the low head side Zone valves should be wired to the Pump Zone Valve Terminal Block Run 24...

Page 19: ...er must be disconnected or otherwise isolated from the gas supply during any pressure testing of the system at test pressures in excess of 1 2 psig Dissipate test pressure prior to reconnecting The bo...

Page 20: ...load pumps in the normal way this will bring power to the pump control block Pumps can be switched on off using the keypad so there is no need for temporary pump wiring during system filling air purgi...

Page 21: ...cting aquastat can use one of these to cause a full boiler shutdown in the case of excess floor temperature contacts for indoor and outdoor temperatures sensors associated with Reset Heating A 10K ohm...

Page 22: ...gement of boiler operations including 1 power up set up boiler state machine standby heat call management etc 2 burner pumps primary external and or zone valve management 3 temperature and throttle op...

Page 23: ...a menu based system described in the following sections 2 4 ACCESS LEVELS The controller provides for the display of further information via the Load Status Screen plus three levels of access for the...

Page 24: ...arget vs boiler supply A record of the service history is also available for onscreen access 2 4 3 Advanced Setup This access level is set for the sole use of factory representatives and is permanentl...

Page 25: ...e fan starts and automatically adjusts to a level suitable for ignition Ten seconds later the pump starts After a total of 15 seconds the ignition cycle begins Interpurge The boiler enters an interpur...

Page 26: ...BH minimum input rating The following default differentials are automatically applied upon initial load characterization DHW and other SetPoint loads 20 F space heating with Outdoor Reset invoked 11 F...

Page 27: ...ch of up to 3 loads over time Multiple heating loads with varying temperature targets are run sequentially as opposed to simultaneously with a mixing valve The objective is to serve each load at the m...

Page 28: ...or a tekmar 070 or similar sensor is shipped with each boiler to be placed in an appropriate outdoor position The temperature management algorithm flexes the boiler supply temperature according to cha...

Page 29: ...n procedure 2 6 3 Variable Speed Pumping One strategy to optimize combustion efficiency across the boiler s wide throttle range is to use a variable speed system primary pump This will better match wa...

Page 30: ...d will drop both the circulating water and the indoor setpoint temperature parameters to 50 F Set Point controlled loads are not adjusted through this process to avoid the potential for boiler cycling...

Page 31: ...and Differential temperature values 2 7 SET UP LOAD DEFINITION After the boiler is powered up the installer can use the keypad and display to characterize the application as follows 1 In the Standby m...

Page 32: ...Mass Radiant Baseboard Air Handler etc An appropriate reset curve is called up through this procedure Reset loads carry a default value for Design Outdoor Temp of 10 F 23 C Raise or lower this as appr...

Page 33: ...st be input they are not automatically assigned as done within some boiler controls Ensure the Maximum takes account of the construction and safety requirements of each application e g 140 F max for t...

Page 34: ...as 29 as rounded to the nearest hundred 16 Two lines below Altitude adjustment is the field for amendment of the primary pump heat purge time To shorten the 5 minute post firing period reduce the 300...

Page 35: ...an to inspect the appliance and to replace any part of the control system and any gas control which has been under water OPERATING INSTRUCTIONS 1 STOP Read the safety information above on this label 2...

Page 36: ...GAS VALVE ADJUSTMENT The VFC modulating boilers are factory calibrated to operate with natural gas or propane if so ordered at sea level The relevant valve adjustment screws have been factory sealed u...

Page 37: ...fire level settings Re define the load as Manual Control Use Heat Output in Configure Load x to control the output as needed 6 At the minimum firing rate adjust the zero offset screw see Fig 12 9 to o...

Page 38: ...n if burner requires cleaning every year In alternate years visually inspect burner through sight glass Ensure flame is stable and without excessive fluttering Normal flame pattern is evenly distribut...

Page 39: ...the bottom 10 of the throttle range e g between 15 000 to 27 500 Btu hr Where a load is heavily weighted to the lowest firing rate and the cycles day count is in excess of 96 day there may be insuffic...

Page 40: ...dels Care should be taken to identify which fan type is needed Gas Valve Type 12 Dungs GB WND 055 D01 S22 Function zero governor gas valve provides strict gas air mixture control over the range 15 150...

Page 41: ...to adjust output according to water temperature Installation use 1 4 nutdriver to loosen ring clamp Install with back curve toward pipe using Honeywell Tradeline 107408 Heat Conductive Compound and re...

Page 42: ...a number of diagnostic features incorporated in the software that evaluate system integrity display error conditions and provide initial suggested remedial actions Section 2 6 6 Error Mode In additio...

Page 43: ...ector at the front of the fan This connector feeds a PWM control signal black wire from the controller and provides a tachometer signal white wire back from the fan Unplugging the connector will cause...

Page 44: ...of the boiler pump will determine the movement of valid sensor values in general inlet pressure will increase while the outlet will decrease when the pump starts Check operation of both sensors by iso...

Page 45: ...ove close to Required Pressure RP if FP only 120 150 vs RP of 250 or 300 then check for actual vent system blockage a disconnect intake within boiler case b open burner then fan gas valve looking for...

Page 46: ...ignition cycle Replace module if no current detected Boiler ignites but shuts off at the end of the ignition trial Improperly grounded pressure vessel burner or unserviceable ignition lead or spark m...

Page 47: ...operation Refer to manufacturer s instructions Check setting with ammeter Air in system or marginal water flow Bleed purge system as required Confirm adequate pump size and temp rise in HX Slow combu...

Page 48: ...nect probe Blown fuse in ignition module Check fuse If blown replace Defective Control Module Check ignition output from control module ii Fan and or pump are off Display not illuminated No power to b...

Page 49: ...n condensate drain Unit cycling on operating safety controls Check operation with Ohmmeter Voltmeter System radiation undersized Check manufacturer s rating tables for capacity per foot Temperature ex...

Page 50: ...IBC Technologies Inc 50 VFC 15 150 and VFC 45 225 Intentionally Blank...

Page 51: ...IBC Technologies Inc 51 VFC 15 150 and VFC 45 225 5 DIAGRAMS See Following Pages 5 1 Parts Diagrams 5 2 Wiring Diagrams 5 3 Sequence of Operations Flowchart...

Page 52: ...enwal 17 Diff Air Press Sensor 17 H401 18 8 Rob n Screw Fenwal 2 18 fas Fen 19 Control Corner Cover 19 CCC 20 6 32 x 0 375 screws 2 20 fas 632 3 8 21 24VAC Transformer 40 VA 21 transform 22 a No longe...

Page 53: ...2 54A PVC 90 54 b Trap PVC elbw 90 2 54B PVC 90 55 a Trap pipe PVC x 2 2 55A PVC x 2 55 b Trap pipe PVC x 2 2 55B PVC x 2 56 a PVC union clean out 56A union 56 b PVC union clean out 56B union 57 a Tra...

Page 54: ...IBC Technologies Inc 54 VFC 15 150 and VFC 45 225 5 2 Wiring Diagram Wiring Diagram for VFC 15 150 and VFC 45 225 Modulating Boilers...

Page 55: ...IBC Technologies Inc 55 VFC 15 150 and VFC 45 225 5 3 Sequence of Operations Flowchart...

Page 56: ...IBC Technologies Inc 56 VFC 15 150 and VFC 45 225 Intentionally Blank...

Page 57: ...lures resulting from abuse accident negligence freezing or acts of God d Damage caused by hard water scale build up excessive oxygenation or external leakage 2 The Phase 2 Warranty excludes all of the...

Reviews: